Solar-Log PRO380-CT - Converter Ratio Adjustment; Connection Diagram for Different Operating Modes

Solar-Log PRO380-CT
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Important note on adjusting the converter ratio.
The converter ratio can only be set once with this meter.
When the meter is connected to power, "Set CT" appears in the display. Once one of the keys has been pressed,
the meter displays the possible converting factors one after another. After the desired converter ratio has been
selected and no more keys have been pressed, the display starts to blink. After 10 seconds, the display switches
from the blinking converting factor mode back to the regular display mode. The converter ratio has now been
set and cannot be modied.
Connection diagram for dierent operating modes
Solar-Log™ PRO380-CT (RS485 or S
0
) connection assignments
The meter connections are labeled IN (bottom) and OUT (top).
As consumption or sub-consumer meter: Connection to the grid (IN) – connection for appliances (OUT)
As inverter /production meter: Connection for the production (IN) – connection to the grid (OUT)
As consumption meter (bi-directional): OUT = connection to the grid – IN = connection to the house/plant
As battery meter (bi-directional): IN = connection to the grid – OUT = connection to the battery
Please note that only Solar-Log™ Pro 380 meters can operate on the RS485 interface (one or several). It is not
possible to combine the operation with other components.
If the meter is the last device on the bus, it has to be terminated at
connection block 22 and 23 with a resistor (120 ohm / 0.25W).
Terminal block connector Solar-Log™ (RS485) PRO380-CT (COM)
Terminal Terminal
1 -> 22 (A)
4 -> 23 (B)
Available settings
For CT Ratio 5/5 40/5 50/5 60/5 75/5 100/5 125/5 150/5 200/5
Choose 5 40 50 60 75 100 125 150 200
For CT Ratio 250/5 300/5 400/5 500/5 600/5 800/5 1000/5 1250/5 1500/5
Choose 250 300 400 500 600 800 1000 1250 1500
For CT Ratio 2000/5 2500/5 3000/5 4000/5 5000/5 6000/5 7500/5
Choose 2000 2500 3000 4000 5000 6000 7500
V1.1
TechnischeDaten:
Nennspannung: 230/400VAC
Strom:0,255(100)A
Frequenz:50Hz
Messgröße:Wirkverbrauch,Rücklaufsperre
Genauigkeitsklasse: B
Eigenverbrauch: <10VA<2W
Breite:4TE(70mm)
ImpulsausgangLED: 10.000Imp/kWh,2,5ms
S0–Impulsausgang: 1.000Imp/kWh,25ms
Arbeitstemperatur: 2Cbis+55°C
Max.rel.Lufeuchte: 75%imMiel,kurzzeig95%
RegistrierteHarmonische: 0,05–0,25kHz
LED:rotblinkend:Bezug>4W,Impulsrate=Verbrauch
Display:6+2Digits(999999,11kWh)
MaximalerLeiterquerschni: Hauptklemmen: max.35mm²
Zusatzklemmen: max.2,5mm²
BaudrateModBus: 9600baud
Anschlussschema:
Zählertyp: PRO380,100A
NachSchaltungstyp1000(DIN43856)
InputL1,L2,L3 ZuleitungseingangPhaseL1,L2,L3
Output„L1,L2,L3“ ZuleitungsabgangPhaseL1,L2,L3
Klemme„N“NeutralleiteranschlussN
Klemmen18,19 S0Impulsausgang„Bezug“(Kl.18=„+“)
Klemmen20,21 S0ImpulsausgangLieferung(Kl.20=+)
Klemme22,23 ModBusAnschlussKlemme22>A,23>B
Klemme24,25 externeTarifumschaltung(230VAC)
KlemmleistensteckerSolarLog PRO380
KlemmeKlemme
1> 22(A)
4> 23(B)
V1.1
AlleAnzeigewertedesZählers:
DurchDrückenderTastenwechseltderZählervonderautomaschrollierendenAnzeige
indiemanuelleAnzeige.HierkönnenmielsTastendruckalleverfügbarenAnzeigewerte
derReihenachaufgerufenwerden.Wirdkeinegedrückt,kehrtderZählernachkurzerZeit
wiederindenautomaschenModuszurück.
InderautomaschrollierendenAnzeigewerdennacheinanderdiefolgenden
Werteangezeigt:
FüreinevollständigeÜbersichtallervergbarenAnzeigewerteimmanuellen
ModusbeachtenSiebiedieausführ lichetechnischeBeschreibungalsDown
loadaufwww.kdkdornscheidt.de.
ÄnderungderModbusAdressemitHilfederSensortastenamhler:
1. MitderlinkenPfeiltastedurchdasMenübläern,bis„addr001
angezeigtwird
2. ZurÄnderungderAdressebeidePfeiltastenfür 5secdrückenAnzeige
blinkt1xauf,wennÄnderungsmodusakvist.
3. MitderrechtenPfeiltasteAdresswerterhöhen,bisgewünschteAdresse
angezeigtwird
4. ZumVerlassendesÄnderungsmodusnochmalsbeidePfeiltastenfür5sec
drücken
5. VerlassendesÄnderungsmoduswirddurchblinkendesDisplaysbestägt
6. SolltedieseBesgungnichterfolgenistGerätimmernochimÄnde
rungsmodus
Bestägungnochmalsversuchen
7. KontrolledereingestelltenAdressedurchannavigierenwie1)
EnergierichtungsanzeigeproPhase123
r=Lieferung(Reverse)F=Bezug(Forward)
WirkenergieBezuginKWh(OBIS:1.8.0)
Saldierend
WirkenergieLieferunginKWh(OBIS:2.8.0)
Saldierend
MomentanLeistung(Gesamt)
Adjustable primary current at 1 Amp secondary current
Transformer ratio 1500/1 1000/1 800/1 250/1 200/1 100/1
Transformer factor 1500 1000 800 250 200 100
Primary current setting 7500 5000 4000 1250 1000 500