Warning!
Only authorized personnel is allowed to set the connection.
3.3 Dimension
Ø
Dimension
534mm
419mm
201mm
4. Technical Data
4.1 DC input
Max. recommended DC power [W]
Max. DC voltage[V]
Norminal DC operating voltage[V]
Operating voltage range [V]
MPPT voltage range@full load [V]
Max. input current [A]
Max. short circuit current [A]
Start up voltage [V]
Start output voltage [V]
No. of MPP trackers
Strings per MPP tracker
DC disconnection swtich
X3-8.0P-T-N
optional
A:3200/B:6400
1000
600
160-950
231-800
12/24
14/28
140
180
2
A:1/B:2
4.2 AC output
Rated output power [W]
Max.apparent AC power [VA]
Rated grid voltage and range [V]
Rated AC frequency and range [Hz]
Normal AC current [A]
Max. output current [A]
Max. output fault current [A]
Inrush current(A)
THD
Displacement power factor
Feed in phase
8000
8800
11.6
12.8
Object
A DC Switch (optional)
Pocket WiFi/Lan/GPRS (all optional)
DRM
Smart plug (optional)
AC Connector
B
C
D
E
F
G
H
I
J
Description
Waterproof plug
RS 485/ Meter(optional)
USB for Upgrade
Ground screw
12 13
Introduction Technical Data
X3-8.0P-T-D
Model
Model
X3-12.0P-T-N
X3-12.0P-T-D
10000
11000
14.5
15.9
28.3
38
50
<3%
0.8 leading-0.8lagging
three-phase
Max. output overcurrent protection(A)
3/N/PE,230/400 (310-480)
50(45-55)/60(55-65)
PV Connector
X3-10.0P-T-N
X3-10.0P-T-D
X3-15.0P-T-N
X3-15.0P-T-D
A:4000/B:8000
1000
600
160-950
289-800
12/24
14/28
140
180
2
A:1/B:2
A:4800/B:9600
1000
600
160-950
347-800
12/24
14/28
140
180
2
A:1/B:2
A:6000/B:12000
1000
600
160-950
434-800
12/24
14/28
140
180
2
A:1/B:2
X3-8.0P-T-N
X3-8.0P-T-D
X3-12.0P-T-N
X3-12.0P-T-D
X3-10.0P-T-N
X3-10.0P-T-D
X3-15.0P-T-N
X3-15.0P-T-D
12000
13200
17.4
19.1
15000
16500
21.7
23.9
Max. inverter backfeed current to
the array(mA)
0