--- Page
5
Legend & abbreviations
settings by using PRG2 PRG2 controls timer & timer only
PRG2 & DIP Switches 1.2.3
These settings enables you to select one specific timing you want in timed output mode
Our timed output mode supports count down timing in 1~60 seconds as well as 1~60 minutes. (NOT continuous, only preset timer values in
the range is available). See the lookup table below for all available values and their settings.
D1 = DIP Switch 1
D2 = DIP Switch 2
D3 = DIP Switch 3
D1 ___ D2 ___
This setting is changed during boot period
D1 ___ D2 ___
DIP position is in normal working after boot
___ This is RELAY 1 timing value
___ This is RELAY 2 timing value
The timed output value DIP switches position lookup table
D1
OFF
/ D2
OFF
D1
ON
/ D2
OFF
D1
OFF
/ D2
ON
D1
ON
/ D2
ON
D1
OFF
/ D2
OFF
1 3 5 7 9 11 13 15
D1 ON / D2 OFF 16 18 20 22 24 26 28 30
D1
OFF
/ D2
ON
31 33 35 37 39 41 43 45
D1
ON
/ D2
ON
46 48 50 52 54 56 58 60
↓
D3
ON
Above value are in minutes
D3
OFF
Above value are in seconds
For example,
If you need a timed output of 31 seconds (relay turn on for 31 seconds then auto turn off)
set DIP 1
OFF
, DIP 2
ON
, DIP 3
OFF
during boot (see Page 3 - Settings – How to change them?)
set DIP 1
OFF
, DIP 2
OFF
, DIP 3
ON
after boot, then activate relay #1
If you need a timed ouput of 52 minutes (relay turn on for 52 minutes then auto turn off)
set DIP 1 ON, DIP 2 ON, DIP 3 ON during boot (see Page 3 - Settings – How to change them?)
set DIP 1
ON
, DIP 2
OFF
, DIP 3
ON
after boot, then activate relay #2
✔
Information: Timed output mode is entered by DIP Switch 3 in ON position, in normal working mode after boot.
Disclaimer: The timer accuracy depends on factors such as temperature etc, it should be in -0.6% ~ +1.0% range under
-4°F to 131°F temp. (+/-0.3% range under 77°F room temperature)
* Characterized value only, NOT tested in production.
It should be good enough for common purpose, but NOT SUITABLE for applications that requires very precise timing
control.