3
505 HUTCHINSON ROAD
C
UMMING, GA 30040-5860
Quick Start GuideQuick Start Guide
Quick Start GuideQuick Start GuideQuick Start Guide
SOLO Temperature Controller
SL4824 Series
SOLO
Safety Information
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and
national codes that regulate the installation and operation of your equipment. These codes vary from area to
area and it is your responsibility to determine which codes should be followed, and to verify that the equip-
ment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and
standards. We do not guarantee the products described in this publication are suitable for your particular appli-
cation, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional
information, please call us at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was printed. At
Automationdirect.com® we constantly strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time without notice and without obligation. This
publication may also discuss features that may not be available in certain revisions of the product.
AutomationDirect’s SOLO is a single loop dual output temperature controller that can control both heating and
cooling simultaneously. There are four types of control modes: PID, ON/OFF, Manual, and Ramp / Soak control.
D
epending upon the particular model of controller, the available outputs include relay, voltage pulse, current, and
l
inear voltage. There are up to three alarm outputs available to allow seventeen alarm types in the initial setting
mode. SOLO can accept various types of thermocouple, RTD, or analog inputs, and has a built in RS-485
interface using Modbus slave (ASCII or RTU) communication protocol.
O
ther features include:
1/32 DIN panel size
2 part x 4 character 7-segment LED display for Process Value (PV): Red color, and Set Point (SV): Green color
Auto Tuning (AT) function with PID control
Selectable between °C and °F for thermocouple and RTD inputs
0 to 50 °C (32 to 122 °F) operating temperature range
UL, CUL and CE agency approvals
G
eneral Description
Specifications
Box Contents and Unpacking Instructions
Unpack the SOLO temperature controller from its shipping carton. Included in the carton is the temperature
controller, mounting brackets plus hardware and this Quick Start Guide.
Inspect all equipment for completeness. If anything is missing or damaged, immediately call the
AutomationDirect returns department @ 1-800-633-0405.
Inspect the part number to ensure the model received matches the output type required.
WARNING! Electric shock danger
1. To prevent electric shock, do not touch the AC terminals while the power is supplied to the controller.
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in
which a serious human injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with insolation (M3 screw, width is 7.0mm, hole
diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 Nm
(4kgfcm). Applicable wire: Solid/twisted wire of 2 mm, 12AWG to 24AWG. Choose AutomationDirect part numbers
BM-00120, BM-00220 or BM-00320 depending on wire size. Be sure to tighten them properly.
2. Protect the controller from dust or foreign objects to prevent controller malfunction.
3. Do not modify or disassemble the controller.
4. Do not connect anything to the “Not used” terminals.
5. Make sure all wires are connected correctly.
6. Do not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid. (b) High humidity
(c) Vibration and shock. (d) EMI / RFI (e) high temperature.
7. Turn power off when wiring or changing a temperature sensor.
8. Be sure to use wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Use wires with correct resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and
route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity,
dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Make sure power cables and signals from instruments are all installed properly before energizing the controller,
otherwise serious damage may occur.
13. To prevent electric shock, do not touch the terminals in the controller or try to repair the controller when power is
applied.
14. Use a soft, dry cloth to clean the controller. Do not use acid or alkaline liquids for cleaning.
15. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install
the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse
type: Time-lag fuse
16. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcur-
rent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes.
(Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-
use installation.
5
0.94”
(24.0 mm)
1.76”
(44.75 mm)
0.86”
(21.85 mm)
3.93”
(99.8 mm)
0.13”
(3.40 mm)
1.89”
(48.0 mm)
PV
SV
AT
OUT1
ALM
FC
OUT2
SET
4824
SOLO
Controller and Panel Cutout Dimensions
1.76”
[44.8 mm]
1.58”
[40.0 mm]
0.87"
[22.0 mm]
+0.02
-0
+0.6
-0
+0.02
-0
+0.6
-0
2.56”
[65.0mm]
(Min.)
(Min.)
1
2
3
4
5
This Quick Start Guide provides basic information on setting up the SOLO temperature controller. For
advanced setup and communication control as well as free configuration software visit the
A
utomationDirect web site at www.AutomationDirect.com.
S
L4
82
4
S
e
ri
es
Mounting Bracket
and Hardware
SL4824 Temperature
Controller
SL4824
Quick Start Guide
*
Note: The supplied 249 ohm resistor should be installed as shown in the terminal wiring diagrams
i
n section 7 for current input operation.
5011661606-S426
2012-01-12
249 ohm
resistor
Specifications
I
nput Power Requirements
100 to 240 VAC 50 / 60 Hz or 24 VDC
Operation Voltage Range
85 to 264 VAC or 21.6 to 26.4 VDC
Power Consumption
5
VA Max
M
emory Protection
E
EPROM 4K bit, number of writes 100,000
Control Mode
PID, ON/OFF, Ramp / Soak control or Manual
Input Accuracy
L
ess than ± 0.2% full scale (except thermocouple R, S, & B types) Max ± (thermocouple R, S, & B types)
Vibration Resistance
1
0 to 55 Hz, 10 m/s
2
f
or 10 min, each in X, Y and Z directions
S
hock Resistance
M
ax. 300 m/s
2
,
3 times in each 3 axes, 6 directions
Ambient Temperature Range
32°F to 122°F (0°C to 50°C)
S
torage Temperature Range
-
4°F to 149°F (-20°C to 65°C)
A
ltitude
2
000m or less
Relative Humidity
35% to 80% (non-condensing)
RS-485 Communication
Modbus slave ASCII / RTU protocol
T
ransmission Speed
2
400, 4800, 9600, 19.2K, 38.4K bps
IP Rating
IP65: Complete protection against dust and low pressure spraying water from all directions.
(inside suitable enclosure)
A
gency Approvals
UL, CUL, CE (UL file number E311366)
Pollution Degree
D
egree 2 - Normally, only non-conductive pollution occurs.
T
emporary conductivity caused by condensation is to be expected.
Input Types
Thermocouple*
K, J, T, E, N, R, S, B, L, U, TXK (Sampling Rate: 400 ms / per scan)
Platinum RTD
3
-wire Pt100, JPt100 (Sampling Rate: 400 ms / per scan)
Analog
0-50 mV, 0-5V, 0-10V, 0-20 mA*, 4-20 mA* (Sampling Rate: 150 ms / per scan)
Control Output Options
Relay (R)
SPST max. resistive load 3A @ 250 VAC
Voltage Pulse (V)
DC 14V Max, output current 40mA Max
Current (C)
DC 4-20 mA output (Load resistance: Max 600 )
Linear Voltage (L)
D
C 0-10V (Load resistance Min 1K )
*Note: Use only ungrounded thermocouples.
O
utput Specifications
Part Number Input Voltage Output #1 Output #2 / Alarm*
SL4824-RR 100 - 240 VAC Relay - SPST Relay - SPST
SL4824-VR 100 - 240 VAC Voltage Pulse Relay - SPST
SL4824-CR 100 - 240 VAC Current Relay - SPST
SL4824-LR 100 - 240 VAC Linear Voltage Relay - SPST
SL4824-RR-D 24 VDC Relay - SPST Relay - SPST
SL4824-VR-D 24 VDC Voltage Pulse Relay - SPST
SL4824-CR-D 24 VDC Current Relay - SPST
*Output #2 can be configured as control output #2 or as an alarm output
Product Support and Configuration Software
For product support, specifications, and installation troubleshooting, a complete
User Manual can be downloaded from the On-line Documentation area of the
AutomationDirect web site.
For additional technical support and questions, call our Technical Support team
@ 1-800-633-0405 or 770-844-4200.
Configuration software for the SOLO controller is available for free down-
load at www.AutomationDirect.com. The software allows communication
and programming for up to four controllers at the same time. Parameters,
process values, set points and temperature changes can be monitored with
the software. The setup data can be uploaded to the user’s PC via RS-485
communication. The user can monitor the temperature changes of the
controllers from the “PV Monitor” Display.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solo SL4824 Series and is the answer not in the manual?

Solo SL4824 Series Specifications

General IconGeneral
BrandSolo
ModelSL4824 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals