SOLO Temperature Controller
SL4848 Series
SOLO
A
utomationDirect’s SOLO is a single loop dual output temperature controller that can control both heating and
c
ooling simultaneously. There are four types of control modes: PID, ON/OFF, Manual, and Ramp / Soak control.
D
epending upon the particular model of controller, the available outputs include relay, voltage pulse, current, and
l
inear voltage. There are up to three alarm outputs available to allow seventeen alarm types in the initial setting
m
ode. SOLO can accept various types of thermocouple, RTD, or analog inputs, and has a built in RS-485 inter-
f
ace using Modbus slave (ASCII or RTU) communication protocol.
O
ther features include:
•
1/16 DIN panel size
•
2 line x 4 character 7-segment LED display for Process Value (PV): Red color, and Set Point (SV): Green color
•
Auto Tuning (AT) function with PID control
• Selectable between °C and °F for thermocouple or RTD inputs
•
0 to 50 °C (32 to 122 °F) operating temperature range
• UL, CUL and CE agency approvals
General Description
Specifications
O
utput Specifications
Part Number Input Voltage Output #1 Output #2 / Alarm #3* Alarm #1** Alarm #2**
SL4848-RR 100 - 240 VAC Relay - SPST Relay - SPST Relay - SPST Relay - SPST
SL4848-VR 100 - 240 VAC Voltage Pulse Relay - SPST Relay - SPST Relay - SPST
SL4848-CR 100 - 240 VAC Current Relay - SPST Relay - SPST Relay - SPST
SL4848-LR 100 - 240 VAC Linear Voltage Relay - SPST Relay - SPST Relay - SPST
SL4848-RR-D 24 VDC Relay - SPST Relay - SPST Relay - SPST Relay - SPST
SL4848-VR-D 24 VDC Voltage Pulse Relay - SPST Relay - SPST Relay - SPST
SL4848-CR-D 24 VDC Current Relay - SPST Relay - SPST Relay - SPST
SL4848-VV 100 - 240 VAC Voltage Pulse Voltage Pulse Relay - SPST Relay - SPST
SL4848-CV 100 - 240 VAC Current Voltage Pulse Relay - SPST Relay - SPST
SL4848-LV 100 - 240 VAC Linear Voltage Voltage Pulse Relay - SPST Relay - SPST
*Output #2 can be configured as control output #2 or as Alarm #3
**Alarm #1 and Alarm #2 have a shared common
Box Contents and Unpacking Instructions
• Unpack the SOLO temperature controller from its shipping carton. Included in the carton is the temperature
controller, mounting brackets plus hardware and this Quick Start Guide.
• Inspect all equipment for completeness. If anything is missing or damaged, immediately call the
AutomationDirect returns department @ 1-800-633-0405.
• Inspect the part number to ensure the model received matches the output type required.
S
pecifications
I
nput Power Requirements
100 to 240 VAC 50 / 60 Hz or 24 VDC
O
peration Voltage Range
85 to 264 VAC or 21.6 to 26.4 VDC
Power Consumption
5 VA Max
Memory Protection
EEPROM 4K bit, number of writes 100,000
C
ontrol Mode
P
ID, ON/OFF, Ramp / Soak control or Manual
Input Accuracy
Less than ± 0.2% full scale (except thermocouple R, S, & B types) Max ± 3° (thermocouple R, S, & B types)
V
ibration Resistance
10 to 55 Hz, 10 m/s
2
for 10 min, each in X, Y and Z directions
S
hock Resistance
M
ax. 300 m/s
2
,
3 times in each 3 axes, 6 directions
A
mbient Temperature Range
3
2°F to 122°F (0°C to 50°C)
S
torage Temperature Range
-4°F to 149°F (-20°C to 65°C)
Altitude
2000m or less
Relative Humidity
35% to 80% (non-condensing)
RS-485 Communication
Modbus slave ASCII / RTU protocol
Transmission Speed
2400, 4800, 9600, 19.2K, 38.4K bps
IP Rating
I
P65: Complete protection against dust and low pressure spraying water from all directions.
(inside suitable enclosure)
Agency Approvals
UL, CUL, CE (UL file number E311366)
Pollution Degree
Degree 2 - Normally, only non-conductive pollution occurs.
Temporary conductivity caused by condensation is to be expected.
I
nput Types
•
Thermocouple*
K
, J, T, E, N, R, S, B, L, U, TXK (Sampling Rate: 400 ms / per scan)
•
Platinum RTD
3-wire Pt100, JPt100 (Sampling Rate: 400 ms / per scan)
• Analog
0-50 mV, 0-5V, 0-10V, 0-20 mA*, 4-20 mA* (Sampling Rate: 150 ms / per scan)
C
ontrol Output Options
• Relay (R)
S
PST max. resistive load 5A @ 250 VAC
• Voltage Pulse (V)
DC 14V Max, output current 40mA Max
•
Current (C)
DC 4-20 mA output (Load resistance: Max 600 ⏲ )
• Linear Voltage (L)
D
C 0-10V (Load resistance Min 1K⏲ )
*Note: Use only ungrounded thermocouples.
Safety Information
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and
national codes that regulate the installation and operation of your equipment. These codes vary from area to
area and it is your responsibility to determine which codes should be followed, and to verify that the equip-
ment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and
s
tandards. We do not guarantee the products described in this publication are suitable for your particular appli-
cation, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional
information, please call us at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was printed. At
Automationdirect.com® we constantly strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time without notice and without obligation. This
publication may also discuss features that may not be available in certain revisions of the product.
WARNING! Electric shock danger
1. To prevent electric shock, do not touch the AC terminals while the power is supplied to the controller.
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in
which a serious human injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with insolation (M3 screw, width is 7.0mm, hole
diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 Nm
(4kgfcm). Applicable wire: Solid/twisted wire of 2 mm, 12AWG to 24AWG. Choose AutomationDirect part numbers
BM-00120, BM-00220 or BM-00320 depending on wire size. Be sure to tighten them properly.
2. Protect the controller from dust or foreign objects to prevent controller malfunction.
3. Do not modify or disassemble the controller.
4. Do not connect anything to the “Not used” terminals.
5. Make sure all wires are connected correctly.
6. Do not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid (b) High humidity
(c) Vibration and shock (d) EMI / RFI (e) high temperature.
7. Turn power off when wiring or changing a temperature sensor.
8. Be sure to use wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Use wires with correct resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and
route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity,
dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Make sure power cables and signals from instruments are all installed properly before energizing the controller,
otherwise serious damage may occur.
13. To prevent electric shock, do not touch the terminals in the controller or try to repair the controller when power is
applied.
14. Use a soft, dry cloth to clean the controller. Do not use acid or alkaline liquids for cleaning.
15. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install
the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse
type: Time-lag fuse
16. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcur-
rent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes.
(Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-
use installation.