4 Initial operation
Only a qualified electrician (in compliance with BGV A3,
§ 2 Subsection 3; only applies in Germany) may work on the
control unit.
Risk of electric shock
Do not touch live parts (ends of cables, contacts, etc.) while the
control unit is still connected to the power supply.
Only switch the DIP switches when the control unit has been
disconnected from the main power supply.
The control unit can be operated in automatic mode or in conjunction
with safety devices (minimum requirement: “safety contact strip”). If
there are no safety devices, the control unit must only be operated in
dead man mode!
Document initial operation!
• Before starting initial operation, switch all DIP switches to “OFF”
(factory default setting).
4.1 Activating dead man operation
In “dead man” mode, the operator runs for as long as the command
button is pressed. The operator stops as soon as the button is
released. A transmitter will not function when the system is in dead
man mode.
Activate dead man operation: DIP switch 7 “ON”.