RDC vision
en 23
Settings
Mode
Current direction of
travel / position
Reaction to safety
contact strip
Reaction to light barrier
DIP 3 OFF
1
OPEN STOP STOP
DIP 4 OFF CLOSE Door opens fully
Operator reverses for
2 seconds
DIP 3 OFF
2
OPEN STOP No reaction
DIP 4 ON CLOSE Door opens fully
Operator reverses for
2 seconds
DIP 3 ON
3
OPEN STOP No reaction
DIP 4 OFF
ZU
Operator reverses for
2 seconds
Door opens fully
Intermediate position No reaction Door opens fully
DIP 3 ON
4
OPEN STOP No reaction
CLOSE
Operator reverses for
2 seconds
Door opens fully
DIP 4 ON
Intermediate position No reaction Door opens fully
Upper end position for
automatic closing
No reaction
Door closes 5 seconds after
passing through light barrier
DIP 5
OFF Automatic closing after opening process is deactivated through pulse input.
ON
Automatic closing after opening processis activated through pulse input. Stan-
dard value = 20 seconds, can be modified using TorMinal.
DIP 6
OFF Partial opening function deactivated.
ON Partial opening function activated.
DIP 7
OFF Dead man operation deactivated.
ON Dead man operation activated.
DIP 8
OFF Monitoring of motor run time deactivated.
ON Monitoring of motor run time activated.