5. DIP switches
16 DIP
12345678
DIP ON
ST
ATUS
RADI
O
SAFETEY
OnlyswitchtheDIPswitcheswhenthecontrolunithasbeendisconnectedfrom
the mains power supply.
DonotusemetalobjectstooperatetheDIPswitches!
If a change was made from an optical safety contact strip to an electrical 8k2
safety contact strip or vice versa:
1. SetDIPswitch8to"OFF"andleaveitinthispositionforafewseconds.
2. SetDIPswitch8to"ON"again.
3. Programruntimeagain.
(See chapter 4.4 Setting run time / runtime monitoring)
AllDIPswitchesaresetto"OFF"atthefactory.
ThecontrolunitreadsinthesettingoftheDIPswitches
after the control unit is switched on,
duringtheself-test,afterthedoorreachestheendpositions,
in every intermediate position if the door is not running.
5.1 Warning light response while the door is moving
Settings
Mode
Function
DIP1 OFF Warninglightasheswhiledoorismoving.
ON Warning light is permanently switched on while door is moving.
DIP2 OFF
No function
ON
No function