– 40 –
Inverter Air-to-Water Heat Pump
Parameter H (System Parameter)
H01——Auto Start (Yes/NO)
When H01 = 0, the heat pump haven’t the auto restart function for regular ON-OFF. That is to say:
Every time the heat pump is connected to electricity, it is in power OFF status.
When H01 = 1, the heat pump has the auto restart function for regular ON-OFF. That is to say:
When the heat pump is connected to electricity, it will keep the power ON or OFF status before power failure.
H02——Master/Slave Unit
H03——Temperature Unit
H04——4-way Valve Polarity On-Heating/Off-Heating
H06——Frequency Control P Value
H07——Frequency Control I Value
H08——Frequency Control D Value
H09——Min Frequency of compressor
H10——Max Frequency of compressor
H11——Type selection of compressor
H12——Hand Drive Compressor Frequency
H13——PFC Function Enable
H15——Unit Address
Parameter P (Pump Parameter)
In normal modes of cooling, heating and electrical heating, the water pump will be started at least P04 time earlier and shut down
2 minutes later than the compressor. The water pump shall be started all the time during defrosting. The controller starts to inspect
water ow switch after P04-10s. If the water ow switch is inspected as ON for 10s successively, the compressor can be started.
P01——Running Mode
P02——Running Interval Time
P03——Running Duration
P04——Advanced Start Time
P05——Manual-control
P04
P03P02
Pump
2min
P02P03P03 P0
2P
02 P03P02
Compresso
r