IM-P405-39 AB Issue 4
49
10.10.7 TIMER X (1 - 3) MENU
DURATION (valve open time)
Ranges 0 - 999
Default 0
Resolution (steps) 1
Units Seconds
Note: If the mains power supply drops below the required specification, or power down
occurs during a blowdown, the relays will de-energize and close the valve. If the mains
supply is restored after the blowdown time has elapsed, the valve will remain shut until the
next scheduled blowdown time.
START HRS : MINS
Start of blowdown sequence Only available if the duration is greater than 0 seconds
Ranges 00:00 - 23:58
Default 00:00
Resolution (steps) 1
Note: Start time must be less than STOP time
REPEAT HRS : MINS
Period when blowdown is repeated. Only available if the duration is greater than 0 seconds
Ranges 00:00 or 00:30 - 12:00
Default 00:00 (no repeats)
Resolution (steps) 1
Note: The time for the next repeated blowdown. If repeat =00:00,only one blowdown will
occur at start
STOP HRS : MINS
Stop of blowdown sequence. Only available if the duration is greater than 0 seconds
Ranges 00:01 - 23:59
Default 23:59
Resolution (steps) 1
Note: The time (Hrs,Mins) the timer sequence is to stop.
DAYS
(Days blowdown occurs). Only available if the duration is greater than 0 seconds
Ranges SUN MON TUE WED THU FRI or SAT
Default - (None selected)