IM-P405-39 AB Issue 4
51
Format: Byte
Start 1 bit
Data 8 bit
Parity 0 bit
Stop 1 bit
Format: Request frame
Address 1 byte
Function code 1 byte
Start address 2 bytes
Quantity of registers 2 bytes
Cyclic redundancy check (CRC) 2 bytes
Total 8 bytes
Format: Response frame
Address 1 byte
Function code 1 byte (or error code, see below)
Byte count 1 byte (or exception code, see below)
Register data 2 times the quantity of 16-bit register
Error check (CRC) 2 bytes
Total 7 bytes if correct (or 5 bytes if in error)
Only Function Code 03, 'Read holding registers' is allowed.
11. Appendix -
Summary of the Modbus protocol