EasyManua.ls Logo

SPX Marley NC8409 - Schedule of Tower Maintenance

SPX Marley NC8409
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
maintenance
Schedule of Tower Maintenance
Some maintenance procedures may require maintenance personnel to enter
the tower. Each cased face of the tower has a door for access to the interior
of the tower. The NC8401 and NC8402 have a 30" wide by 33" high door.
All other models have a 30" wide by 48" high door.
The optional fan deck ladder is designed and intended solely for personnel to
gain access to the fan deck. The fan deck ladder should not be used to enter
or exit the access doors located on the cased face of the tower unless the
optional access door platform is provided.
The purchaser or owner is responsible for providing a safe method
forenteringorexitingtheaccessdoor.Useofthefandeckladder
toenterorexittheaccessdoorsmayresultinafall.
Included with this instruction packet are separate Service Manuals on each
major operating component of the tower, and it is recommended that you
read them thoroughly. Where discrepancies may exist, the separate Service
Manuals will take precedence.
The following is recommended as a minimum routine of scheduled mainte-
nance:
Always shut off electrical power to the tower fan motor prior to
performing any inspections that may involve physical contact with
themechanicalorelectricalequipmentinoronthetower.Lockout
and tag out any electrical switches to prevent others from turning
thepowerbackon.Servicepersonnelmustwearproperpersonal
protectiveclothingandequipment.
Weekly: Inspect for bacterial growth and general operation conditions. Bacte-
rial growth should be reported to your water treatment expert for immediate
attention.
Monthly (Weekly at start up): Observe, touch, and listen to the tower.
Become accustomed to its normal appearance, sound, and level of vibration.
Abnormal aspects relating to the rotating equipment should be considered
reason to shut down the tower until the problem can be located and corrected.
Observe operation of the motor, coupling (or drive shaft), Geareducer and
Warning
Warning