EasyManua.ls Logo

Status Instruments DM4000U - Page 45

Default Icon
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
root 52 ( Power 5/2. See 4.2.2.15 )
default setting: LinEAr
4.2.2.13 User linearisation
Selection of this option for Cond allows access to the User submenu. Within this
menu, thirteen points may be programmed to relate electrical input to engineering
value. These points are represented by IN and OUT entries within the menu, where IN
are the electrical inputs and OUT the resultant engineering value. An example of a user
linearisation utilising all thirteen points is shown below.
There are a few rules which should be followed when using this facility.
a) The HI and LO values for engineering range should have been set before any
entry of data. Any engineering values entered should lie between HI and LO.
b) The entries for the electrical inputs should progressively increase. There is no
such restriction on the engineering units.
c) If not all thirteen points are used, it is necessary to reproduce the values in the
last entry in entry 13.
INPUT MENU
PROGRAMMING
Page 45