GP Series
Portable Chillers
Part Number: 882.93092.00
Bulletin Number: SC2-620
Effective: 5/1/2009
Write Down Your Serial Numbers Here For Future Reference:
_________________________ _________________________
_________________________ _________________________
_________________________ _________________________
We are committed to a continuing program of product improvement.
Specifications, appearance, and dimensions described in this manual are subject to change without notice.
ECN No. ____________
© Copyright 2009
All rights reserved.

Table of Contents

Questions and Answers

  • A
    Ashley SanchezJul 29, 2025
    How to troubleshoot a Sterling GP Chiller that does not run?
    • L
      Lisa HunterJul 29, 2025
      If your Sterling Chiller unit isn't running, several factors could be at play. First, ensure the unit is receiving power by checking the main disconnect, fuses, wiring, and power lead. Verify that the voltage supplied is within plus or minus 10% of the nameplate rating. Also, inspect the on/off switch and replace if defective. Examine the control circuit fuse and replace it if blown. Check the transformer and look for a short circuit. Replace the control transformer if it's defective. Ensure the piping flow switch circuit is not open by adding water or a water/glycol solution if needed. Finally, check if the pump motor is off due to an overload; if so, reset and test it.
  • D
    Dustin RojasAug 2, 2025
    Why is the water temperature too high in my Sterling GP Chiller?
    • S
      Sean WattsAug 2, 2025
      If the water temperature in your Sterling Chiller is too high, there are a few things to check. First, ensure that the water/glycol mixture is adequate for your process. Next, verify that the leaving fluid temperature, warning, or fault set point is properly set and adjust if necessary. Finally, a low refrigerant charge could be the cause, in which case you should call a service technician to find and repair the leak, and then add refrigerant.
  • W
    wandabondAug 6, 2025
    What to do if Sterling GP runs continuously but has weak cooling?
    • M
      Marcus MorrisAug 6, 2025
      If your Sterling Chiller runs continuously but doesn't provide enough cooling, start by cleaning the filters to address restricted condenser airflow. Clean the condenser. Check the refrigerant charge to ensure the unit isn't low on refrigerant. If these steps don't resolve the issue, the compressor may not be operating efficiently, requiring a service call. It's also possible that the unit is undersized for the application, in which case you should contact a sales representative.
  • C
    Caroline GregoryAug 10, 2025
    Why is the compressor not running on my Sterling GP Chiller, but the pump is?
    • D
      David FitzpatrickAug 10, 2025
      If the pump in your Sterling Chiller runs but the compressor doesn't, start by lowering the leaving fluid temperature below the desired leaving temperature. If that doesn't work, the leaving fluid sensor High/Low thermostat may be defective and need replacement. Allow the compressor time to cool and reset, then check for high/low voltage, ensuring it's within plus or minus 10% of the nameplate rating. Check for open fuses and loose compressor electrical connections. The compressor contactor holding coil might be open, requiring repair or replacement. Similarly, a defective compressor auxiliary contact will need repair or replacement. Lastly, look for and repair any broken wires in the compressor control circuit.
  • R
    Reginald StevensAug 14, 2025
    What causes short cycling of the compressor in a Sterling GP?
    • C
      Christopher BrownAug 14, 2025
      If the pump runs, but the compressor cycles at short intervals in your Sterling Chiller, first clean the plugged Y-strainer. If that doesn't solve the issue, the hot gas may not be coming on, requiring replacement of the relay board on the control board hot gas coil. Also, low water flow could be the problem, so install a bypass between the to-and-from process line.
  • D
    Dana MyersAug 19, 2025
    How do I fix low pump pressure in my Sterling GP Chiller?
    • B
      berrystephanieAug 19, 2025
      If the pump pressure is low in your Sterling Chiller, verify the pump rotation. If it's running in reverse, reverse any two main power leads and re-verify for correct pump rotation. Also, check for any foreign matter in the system and clean it.
  • E
    Elizabeth FowlerAug 23, 2025
    What causes high pump pressure in a Sterling GP?
    • J
      Jeffrey GainesAug 23, 2025
      If the pump pressure is too high in your Sterling Chiller, it is likely due to restricted water flow. Check for partially closed valves and ensure all lines are properly sized.

Summary

Chapter 1: Safety

Safety Symbols and Alerts

Explanation of danger, warning, and caution symbols.

General Safety Precautions

Essential safe practices for installation, operation, and maintenance.

Operator Safety Responsibility

Emphasizes the operator's role in ensuring safe operation.

Chapter 2: Functional Description

Safety Devices and System Interlocks

Explains safety mechanisms like pressure cutouts and flow switches.

Key Safety Device Functions

Focuses on high/low pressure cutouts and flow switches.

Chapter 3: Installation

Electrical Connections

Instructions for making proper electrical connections.

Checking Motor Direction

Verifying correct motor rotation for compressors, pumps, and fans.

Automatic Water Make-Up and Initial Start-Up

Connecting make-up systems and performing initial startup checks.

Finishing Setup: Setting Up Passwords

Procedure for setting operator and supervisor passwords.

Chapter 4: Operation

Controller Interface and Buttons

Overview of the microprocessor controller and its buttons.

Initial Start-up Sequence

Verifying startup checklist and initiating operation.

Setting Operator Setpoints

Navigating to setpoints and adjusting values.

Controller Setpoints Details

Table detailing variables, descriptions, and access levels for setpoints.

Chapter 5: Maintenance

Chapter 6: Troubleshooting

Unit Not Running or Compressor Issues

Diagnosing problems when the unit fails to start or the compressor has issues.

Pressure and Cooling Performance Issues

Diagnosing high/low pump pressure and insufficient cooling.

Sterling GP Series Specifications

General IconGeneral
RefrigerantR-410A
Compressor TypeScroll
Energy Efficiency Ratio (EER)Up to 12.0 (depending on model and conditions)
Voltage Options208-230/460V, 3-phase
Control SystemMicroprocessor-based
DimensionsVaries by model
WeightVaries by model