INSTALLATION
Settings
www.stiebel-eltron.com VRC-W 400 (E) | 17
ENGLISH
12. Settings
When you enter a four-digit code, additional actual values become
visible, which were hidden beforehand.
12.1 Parameter
P28: Delivered condition OFF
VRC-W 400 VRC-W 400 E
Description Code Unit Min. Max. Options Stand-
ard
Min. Max. Options Stand-
ard
P1 Set room temperature A0 °C 5 28 20 5 28 20
P2 Intensive ventilation runtime A0 Min. 1 240 30 1 240 30
P3 Bypass mode A0 0 | 1 | 2 | 3 2 0 | 1 | 2 | 3 2
P4 Reset filter A0 0| 1 - 0| 1 -
P6 Flow rate, stage0 A1 m³/h 40 150 60 40 150 60
P7 Flow rate, stage 1 A1 m³/h 60 300 140 60 300 140
P8 Flow rate, stage 2 A1 m³/h 60 400 200 60 400 200
P9 Flow rate, stage 3 A1 m³/h 60 400 260 60 400 260
P14 Supply air flow rate offset A1 -100 100 0 -100 100 0
P15 Humidity protection interval A1 h 1 24 1 1 24 1
P16 Start-up time for humidity measurement A1 min 5 15 5 5 15 5
P17 Extract air humidity limit A1 % 5 95 65 5 95 65
P18 Frost protection temperature A1 °C -10.0 10.0 4.0 -10.0 10.0 4.0
P19 Filter change interval A1 d 1 365 90 1 365 90
P22 Enable preheater A1 0 | 1 1 0 | 1 1
P23 Frost protection mode A1 0 | 2 2 0 | 2 2
P24 Bypass enable temperature A1 °C 5.0 15.0 10.0 5.0 15.0 10.0
P25 Bypass blocking temperature A1 °C 5.0 15.0 8.0 5.0 15.0 8.0
P26 Bypass hysteresis A1 K 0.0 5.0 2.0 0.0 5.0 2.0
P27 Temperature differential for enabling the bypass A1 °C 0.0 5.0 2.0 0.0 5.0 2.0
P28 Enable fan A0 On | OFF On On | OFF On
P29 Appliance type A1 9 10
P30 Temperature for enabling frost protection A2 °C -10.0 10.0 -3.0 -10.0 10.0 -3.0
P31 Enabling of humidity-dependent flow rate control A1 0| 1 0 0| 1 1
P32 Enable outdoor air condensate prevention A2 0 | 1 0 0 | 1 0
P33 Temperature offset for condensate prevention A2 K -5.0 5.0 0.0 -5.0 5.0 0.0
P35 Bypass function cooling/heating A2 1 | 2 | 3 1 1 | 2 | 3 1
P70 Delete fault list A1 0| 1 - 0| 1 -
P80 Day A0 1 7 1 7
P81 Time A0 00:00 23:59 00:00 23:59
P82 Level of lighting A0 2 10 10 2 10 10
P83 Mode of backlighting A0 Auto | On | OFF Auto Auto | On | OFF Auto
P84 Illumination duration A0 s 10 500 60 10 500 60
P85
Lower standard display
A0
OFF | Time | Set room
temperature | Extract
air temp. | Extract air
humidity
OFF
OFF | Time | Set room
temperature | Extract
air temp. | Extract air
humidity
OFF