10 |WPL 33 www.stiebel-eltron.com
INSTALLATION
Installation
9.4 Electrical installation
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
WARNING Electrocution
Only use a permanent connection to the power supply.
Ensure the appliance can be separated from the power
supply by an isolator that disconnects all poles with at
least 3 mm contact separation. This requirement can be
met with contactors, circuit breakers, fuses/MCBs, etc.
Note
The specified voltage must match the mains voltage.
Observe the type plate.
Route cables with the following cross-sections in accordance with
the respective fuse rating:
MCB/fuse
rating
Conductor cross-section
16 A
2.5 mm²
1.5 mm² with only two live wires and routing on a wall or in an
electrical conduit on a wall.
The electrical data is provided in the chapter "Specification" . The
BUS cable requires a cable J-Y (St) 2x2x0.8mm².
!
Material losses
Provide separate fuses/MCBs for the three power circuits
of the appliance, the control unit and the electricemer-
gency/booster heater.
!
Material losses
Provide common fuses/MCBs for the control cable of the
appliance and the heat pump manager.
9.5 Buffer cylinder
A buffer cylinder is recommended to ensure trouble-free appliance
operation.
The buffer cylinder is not only installed to provide hydraulic sep-
aration of the flow rates in the heat pump circuit and the heating
circuit, but also as an energy source for defrosting.
10. Installation
10.1 Transport
Pay attention to the appliance's centre of gravity when trans-
porting the appliance.
- The centre of gravity is in the area where the compressor is
located.
- Lifting slings for handling the standard appliance can be
hooked in anywhere on the bottom of the frame.
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport only do so
for a short time on one of its longitudinal sides.
- The longer the appliance is tilted, the greater the distribution
of refrigerant oil in the system.
Wait approximately 30minutes before starting the appliance
after it has been tilted.
10.2 Siting and connecting the appliance
Note
- Two screws are available at the top of the appliance
frame to secure the cover.
- In the frame at the bottom, one screw is available on
each side to secure the side panels.
Wind the sixscrews out of the appliance frame and keep them safe.
!
Material losses
After installing the heat pump, tighten the pipe fittings
on the pressure and inlet lines of the compressor with a
torque of 100Nm.
2
1
26_03_01_0670
1 Pressure line fittings
2 Suction line fittings