E/0204/39/7
* Ambient temp. 35°C; Inside cabinet temp. 25°C RH 40%
** measured at 2m distance from the unit front, free field, unit operating in cooling mode at nominal conditions. Referred to type 1.
*** Type 1: with free cooling & emergency ventilation; DC fans;
Type 2: cooling only; with AC fans
Technical Data Split-Air CST 60 / 80
Cooling capacity *
Sensible cooling capacity*
Refrigerant
Refrigerant charge
Condenser fan
Number / Type
Air flow
External static pressure
Evaporator fan (Type 1)***
Voltage
Number / Type
Air flow
External static pressure
Evaporator fan (Type 2)***
Number / Type
Air flow
External static pressure
EER index (type 2)*
Outside operating limit temp. min/max
Shelter operating limit temp. min/max
Duty cycle
Outdoor unit
Noise level**
Weight
Height / Width / Depth
Indoor unit type 1
Noise level**
Weight
Height / Width(with brackets) / Depth
Indoor unit type 2
Weight
Height / Width(with brackets) / Depth
kW
kW
kg
m³/h
Pa
V
m³/h
Pa
m³/h
Pa
W/W
°C
°C
%
dB(A)
kg
mm
dB(A)
kg
mm
kg
mm
CST 60
6.4
5.6
R407c
2.5
1 / 420 axial
2800
5
24DC / 48DC
1 / 310 radial
1400
10
1 / 310 radial
1400
40
2.47
-20/+45
+20/+40
100
56
80
640/950/400
63
90
375/956/1300
85
375/956/1000
CST 80
8.4
7.8
R407c
3.2
1 / 450 axial
3400
5
24DC / 48DC
2 / 280 radial
2150
5
2 / 310 radial
2150
60
2.74
-20/+45
+20/+40
100
60
80
640/950/400
69
90
375/956/1300
85
375/956/1000