E/0204/39/9
CST 60 CST 80
Electrical Data Split-Air CST 60 / 80
* Ambient temp. 35°C; Inside cabinet temp. 25°C RH 40%
** Type 1: with free cooling & emergency ventilation; DC fans;
Type 2: cooling only; with AC fans
Outdoor Unit
Power Supply Code
Nominal voltage
Tolerance on voltage
Phase
Frequency
Tolerance on frequency
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)*
Control voltage
Compressor
Power consumption*
Operating current (OA)*
Max. current (FLA)
Locked rotor current (LRA)
Condenser Fan
Power consumption*
Operating current (OA)*
Indoor Unit Type 1**
Voltage
Tolerance on voltage
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Evaporator Fan
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Indoor Unit Type 2**
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Evaporator Fan
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
00
230
220-240±10%
1
50
±2%
2.5
11.3
61.7
24
2.29
10.6
14.8
61
42
400
380-420±10%
3+N
50
±2%
2.5
4.8
32.7
24
2.29
4.1
5.1
32
V
V
ph
Hz
kW
A
A
Vac
kW
A
A
A
kW
A
VDC
VDC
kW
A
A
kW
A
A
kW
A
A
kW
A
A
00
230
220-240±10%
1
50
±2%
2.8
13.0
76.9
24
2.6
12.1
17.3
76
42
400
380-420±10%
3+N
50
±2%
2.8
5.6
40.9
24
2.6
4.7
6,2
40
0.16
0.74
24 / 48
22-28 / 43-56
0.13 / 0.13
5.73 / 2.98
12.25 / 6.12
0.1 / 0.1
4.48 / 2.35
11 / 5.5
0.14
0.63
1.5
0.14
0.63
1.5
0.19
0.92
24 / 48
22-28 / 43-56
0.2 / 0.2
9.68 / 4.84
17.25 / 10.23
0.2 / 0.2
9.68 / 4.84
2 x 8 / 4.8
0.28
1.27
2 x 1.5
0.28
1.27
2 x 1.5