EasyManua.ls Logo

Sullair SRC - Outputs; User Interface

Sullair SRC
57 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SRC Service Manual
Revision 02
Aug 2007
Page 23 of 56
4.3.2 Outputs
All outputs are digital.
Digital Outputs (J1 & J3)
J1 1 Common
J1 4 NO1 Compressor Contactor (KM1)
J1 6 C4 Alarm (Common)
J1 7 NO2 “Dryer On” Relay (KA2)
J1 9 NO4 Alarm/Warning (N/O) Contact
J1 10 NO3 Drain Solenoid Valve (YV1)
J1 12 NC4 Alarm/Warning (N/C) Contact
4.3.3 Electrical Specifications
Power Supply 24 Vac ± 20%
Temperature Sensor (B1 & B2) Reading Range -10
o
C to +90°C ± 1°C
Input for High & Low Pressure & Remote On-Off 24 Vac
Output for Drain Level Sensor 5Vc.c. - 15mA
Output to KM1, YV1 & KA2 V
max
30Va.c. - I
max
1A
Output for Alarm/Warning V
max
30Va.c. - I
max
1A
4.3.4 User Interface
On – Off
Switch
Energy Saving Indicator
Digital Display
Control Buttons
The main control panel of the dryer consists of:
On/Off Switch with door block,
7-segment, 3-digit digital display,
4 LED Lights, and
4 Buttons.

Other manuals for Sullair SRC