SRL Service Manual 
Revision 00 
July 2007 
 
Page 48 of 56 
 
10.2.12 S
ervice required (Warning) 
 
What it means:  Dryer has on for longer than the Service Required Warning Interval (Parameter 
B9: Default 6000 hours) without service or inspection. 
What it does:  Cuts power to the alarm contacts. Turns on Warning Light & alternates between  
“Sr” and the dewpoint reading on the digital display.   
To Reset:  Press ALARM RESET. Power restored to alarm relay & Warning Light goes off 
for 24 hours. 
To reset the alarm for another 6000 hours, contact Sullair or your authorized 
Sullair distributor and ensure the dryer & filters are inspected and maintained in 
accordance with the schedules in their respective user guides. 
The alarm reset (Parameter B3) and it’s interval (Parameter B9) are locked and 
can only be modified after entering a special pass code. See Section 10.3 for 
further information.  
Notes:     Unlike the other alarms, the “Sr” warning is not recorded in the alarm history.