OM Series Quarter-turn Electric Valve Actuator - Modulating Control
The power must be off during this procedure so as to
avoid damage to the actuator.
Do not make adjustments to the mechanical end stops
when actuator is in motion.
All steps below must be completed before normal
a. Turn power off.
b. Loosen the locknut and unwind
both Open and Close Mechanical
end stop screws for 7 turns.
c. Loosen the M5 set screw on the
sector gear or round gear.
【
】
e. Supply power to the fully-open position. Screw in the Open
(left) Mechanical end stop screw until it bottoms out, and then
turn back for 3/4-1 turn based on the actuator model listed below.
OM-2 to OM-6, OM-F, OM-G and OM-H:1 turn.
OM-7 to OM-8:3/4 turn.
OM-9 to OM-13:1/2 turn.
f. Tighten the locknut.
g. Supply power to the fully-closed position. Screw in the Close
(right) Mechanical end stop screw until it bottoms out, and then
turn back for 3/4-1 turn based on the actuator model listed below.
OM-2 to OM-6, OM-F, OM-G and OM-H:1turn.
OM-7 to OM-8:3/4 turn.
OM-9 to OM-13:1/2 turn.
h. Tighten the locknut of mechanical end stops.
i. Supply the power to confirm that the limit switches achieve the
fully open-close stroke.
j. Supply power to run the actuator to the fully-closed position.
Adjust the gear and the set screws based on the actuator model
listed below.
OM-A and OM-AM:Rotate the round gear counter-clockwise
to the end and tighten the M5 set screw.
OM-1:Rotate the round gear clockwise to the end and tighten
the M5 set screw.
OM-2 to OM-13, OM-F, OM-G and OM-H:Rotate the sector
gear clockwise to the end and tighten the M5 set screw.
k. The setting procedure is now completed.
TC2”CLOSE”
TC1”OPEN”
:increase closing degree.
Counter-clockwise:decrease closing degree.
Clockwise:decrease opening degree.
Counter-clockwise:increase opening degree.
TC2”CLOSE”
TC1”OPEN”
Clockwise:decrease closing degree.
Counter-clockwise:increase closing degree.
Clockwise:increase opening degree.
Counter-clockwise:decrease opening degree.
【OM-2 to OM-13, OM-F, OM-G and OM-H】
TC2”CLOSE”
TC1”OPEN”
Clockwise:decrease closing degree.
Counter-clockwise:increase closing degree.
Clockwise:increase opening degree.
Counter-clockwise:decrease opening degree.
Set Screw M5
【OM-2 to OM-13, OM-F, OM-G and OM-H】
OM-A, OM-AM & OM-1 (The layout is based on 110 /
220V.)
Modulating Control Board Adjustment
▲Turn power off before adjusting below settings.
VR52
Sensitivity Switch
VR51
d. Refer to below illustrations to adjust the TC1 - TC4 to set
the fully-open and fully-closed position.