· The DC voltage can be up to 750 V. The
unit may only be opened by a qualified
electrician!
· Always disconnect the PV generator side
first by opening the PV generator switch,
and then the grid connection by isolating
the relevant mains fuse!
· If you do not have a PV generator switch
in your PV system, you must disconnect
the grid connection first of all by isola-
ting the relevant mains fuse. However, a
«grid error» will be entered in the error
memory of the solar inverter!
· Disconnection of the PV generator by
removing the TYCO SOLARLOK DC con-
nectors must never be performed under
load. In the event of non-compliance, the
connectors could be damaged by a strong
electric arc. In this case, the relevant con-
nectors must be replaced!