CAUSE #1:
Solenoid is not receiving power
SOLUTION:
Place your fingers around the solenoid
coil to see if it is receiving power. There should
be a slight vibration and humming. If not, verify
that there is output at the controller by using a
volt meter. If there is electrical output (24 VAC)
then the problem is either a bad coil or broken
wire. Check the coil by disconnecting solenoid
lead wires from valve wires and measure ohms
with an ohm meter. A reading of 24 to 27 ohms
means the coil is OK. If reading is 0 or infinity,
replace coil.
CAUSE #2:
Enlarged inlet orifice at bottom of
diaphragm shaft is allowing water to enter
diaphragm chamber at a rate greater
than it can exit through solenoid exhaust
port. Because the inlet orifice is brass, it
can enlarge over time in high
pressure/velocity conditions.
SOLUTION:
Replace diaphragm assembly (which
includes diaphragm shaft) or replace
adaptor.
14
Troubleshooting
PROBLEM: Valve will not open
when energized.