3. TO SET ALL THE OTHER PARAMETERS
a. Press and hold SET and UP buttons
b. AL1 (Alarm) - is shown (value 0 to 50). Set to zero.
c. Press SET
d. SC (Measurement update freq. Val -20 to +20). Set to zero to 4.
e. Press SET
f. P(Proportional band – 0 to 100%). Set to 5
g. Press SET
h. I (Integration time – 0-999). Set to 300
i. Press SET
j. D (Differential time – 0 to 999). Set to 20
k. Press SET
l. At (Self-starting mode). Set to ON
m. Press SET
n. Lin (No idea – range 20 to 100). Set to 100
o. n25 (No idea – range 0 to 999). Set to 400?
p. Press SET
q. dPu (No idea – range 0 to 20). Set to zero
r. Press SET
s. LoC (Lock on/off). 0=off/1=set temp only/ 2=all locked
t. Press SET
u. Return to operation