14. Specifications
120V MODEL
UPS-3000-OL
120 VAC (80 - 138V at 100% load) 60-138V at 40% load
Capacity VA (W) 1500 VA (1050 W) 2000 VA (1400 W) 3000 VA (2100 W)
Frequency 60 Hz
Power Factor ≥ 0.97
Topology True on-line, Double conversion, Input PF correction
Linear ≤ 5%; non-Linear ≤ 10%
Sine wave, zero transfer time
Efficiency AC/DC/AC ≥90%
Auto Restart Yes
Start on Battery Yes
Rated Current 12.5 A 16.6 A 25 A
110-150% for 30 sec, ≥ 150% for 200 msec
Battery Type (UPS)
(8) 12V 7.2AH / 96V
Backup Time
7-11 min (internal batteries) to 18 hours using External Battery
Packs (EBP)
Battery Type (EBP)
2 strings of (4) 12V
7.2 AH / 48V