PLUMBING
Condensate drains should be connected to a waste or reclamation system in
order to direct the condensate out of the space. Ensure condensate lines remain
unobstructed to avoid unattended spillage or drain pan overflow. Use of a p-trap
(reference figure 2) is required to avoid pressure and vacuum related issues, which
can negatively aect condensate drainage. Following plumbing installation, the
system should be checked for leaks prior to attempting unattended operation.
Insulate the condensate drain a minimum of 72 inches (182.8 cm) from the unit to
avoid condensate pooling on the bottom of the drain pipes and dripping.