3.3 Integer Value (R/W): IV W
Object
Instance
Object Name Min/Max
1 Speed Mode 0-3
Communication determines speed (0=NO 1=Predened Speed I-II-III 2=TIMETABLE 3=set
values in objects)
2 Speed Select - I II III 0-3
Selection of predened speed (0=OFF 1=LOW 2=MEDIUM 3=HIGH)
3 MANU/AUTO 0-1
MANUAL/AUTO mode (0=MANUAL 1=AUTO/Time scheduler)
4 Set Speed Supply 0-99999
Set supply Flow (m3/h or l/s) or Torque (%)
5 Set Speed Exhaust 0-99999
Set exhaust Flow (m3/h or l/s) or Torque (%)
6 Force Bypass 0-2
Override: force bypass ON or OFF, 0=normal, 1=force_on, 2=force_o
7 BOOST 0-1
force boost mode, 0/1
8 Cool Stop 0-1
Override: force cooling to stop if set to 1. Note that cooling will start if this object is set to
0 and if Heat Stop object is set to 1.
9 Heat Stop 0-1
Override: force heating to stop if set to 1.
10 Control Board Reset 0-1
Do RESET of controller, clear alarms (0=NO, 1=RESET). Autoreset
1 Running Hours Reset 0-1
Do reset of run time, working hours (0=NO, 1=RESET). Autoreset
12 Filters Hours Reset 0-1
Do reset of lters hours (0=NO, 1=RESET). Autoreset