EasyManuals Logo

System Sensor APA151 User Manual

System Sensor APA151
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
D640-02-00 1 I56-2964-002
APA151 Annunciator
with Piezo Alert
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
NOTICE: These models were only tested at the 16-33 Volt
DC limits. This does not include the 80% low-end or 110%
high-end voltage limits. This manual shall be left with the
owner/user of this equipment.
General Information
The National Fire Protection Association (NFPA) has pub-
lished codes, standards, and recommended practices for the
installation and use of this product. It is recommended that
the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority
having jurisdiction. For further information, consult NFPA
72 and 90A requirements.
The System Sensor APA151 annunciator with piezo alert
is an audible signal appliance for fire alarm service. It is
intended for use in System Sensor 4-wire conventional duct
smoke detector applications without a system control panel
to comply with NFPA 90A.
The APA151 provides a red alarm LED, with an audible an-
nunciation of an alarm signal, and a green power LED.
Specifications
Dimensions: 4.6˝ L × 2.9˝ W × .45˝ D
Weight: .17 lbs.
Electrical Requirements:
Voltage: Regulated 24VDC
Operational Voltage: 16–33 VDC
Maximum Operating Current: 30mA
Connections: #6 binding head screws, 12 AWG to 18 AWG wire
UL Reverberant Room: 81 dBA min. @ 10 ft.
Standard Operating Temperature: 0°C to 49°C (32°F to 120°F)
Humidity Range: 10% to 93% non-condensing
Figure 1:
A0360-01
I56-2964-002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the System Sensor APA151 and is the answer not in the manual?

System Sensor APA151 Specifications

General IconGeneral
BrandSystem Sensor
ModelAPA151
CategorySecurity System
LanguageEnglish

Related product manuals