EasyManua.ls Logo

System Sensor RTS151 - User Manual

System Sensor RTS151
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
D440-01-00 1 I56-0469-011
NOTE: RTS151 replaces RTS451.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 mod-
els. For D2 models order part #DCoil. For the DH400/500 models order part
is #Coil.
GENERAL INFORMATION
System Sensor’s RTS151 is an automatic fire detector accessory designed to
test a remotely located detector. Consult detector installation instructions for
additional information.
The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of the above product. It is
recommended that the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority having jurisdiction.
RTS151 CONTENTS
1 RTS151 remote test station
1 screw pack (2 mounting screws)
1 M02-04 test magnet
WIRING OF RTS151
Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151 mounts to a single gang box (2
1
/2minimum
depth), or directly to the wall or ceiling.
See Figure 8 for wiring diagram of RTS151 with Duct Smoke Detectors.
In Canadian applications, the RTS151 is intended to be located in the same
room as the smoke detector and within 60 feet of the unit.
OPERATION
Test Function
Place and hold the painted side of the magnet to the test location RTS151.
Alarm Indication
With the magnet in place some time will elapse (40 sec. maximum) depend-
ing on the detector type, before the alarm indicating LED will light.
Reset Function
Gently insert a
1
/8˝ maximum diameter tool into the hole until it stops and
LED turns off. The RTS151 is capable of resetting only certain System Sensor
models of detectors. Refer to detector installation instructions for additional
information.
SPECIFICATIONS
Dimensions: 4.8˝ H × 2.90˝ W × 1.4˝ D
Weight: .16 lbs.
Power Requirements
Alarm LED: 2.8 – 32 VDC, 10 mA max.
Coil Current: 95 mA max.
Test Switch: 10 VA @ 32 VDC
Reset Switch: 10 VA @ 32 VDC
Alarm Response Time: 40 sec. max.
Temperature: –10°C to 60°C (14°F to 140°F)
Humidity: 95% RH Non-condensing Max
TEST
RESET
FIGURE 1. RTS151 REMOTE TEST STATION:
FIGURE 2. WIRING DIAGRAM FOR RTS151 TO D4120 4-WIRE DUCT
SMOKE DETECTOR:
FIGURE 3. WIRING DIAGRAM FOR RTS151 TO D2-2WIRE DUCT
SMOKE DETECTOR:
RTS151
Remote Test Station
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
H0196-01
H0582-11
I56-0469-011
2
1
5
4
3
D4120
RTS151
(RED LED)
ALARM
FIELD
INSTALLED
JUMPER
AUX OUT +
AUX OUT
ALARM
R TEST
R RESET
EXTERNAL
(-) POWER (+)
SUPPLY
*
RTS151
REMOTE TEST STATION
LED OPTION
1 PER UNIT
10mA CURRENT DRAW
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
45
321
TEST COIL +
TEST COIL
COMM +
OUT (CONV ONLY) +
COMM –
RA/RTS –
RA +
RTS +
NOTE: THE RTS151 TEST COIL CIRCUIT
REQUIRES AN EXTERNAL 24 VDC POWER
SUPPLY WHICH MUST BE UL LISTED.
NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE
INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL,
SOLD SEPARATELY.
H0571-08
Question and Answer IconNeed help?

Do you have a question about the System Sensor RTS151 and is the answer not in the manual?

Summary

Specifications

General Information

RTS151 Contents

Wiring of RTS151

Wiring Diagram for RTS151 to D4120 4-Wire Duct Smoke Detector

Illustrates the connection of the RTS151 to a D4120 4-wire duct smoke detector.

Wiring Diagram for RTS151 to D2-2 Wire Duct Smoke Detector

Shows how to wire the RTS151 to a D2-2 wire duct smoke detector, including test coil connections.

Operation

Test Function

Procedure for activating the test function using a magnet on the RTS151.

Alarm Indication

Describes the delay before the alarm LED lights up when the test function is active.

Reset Function

Instructions for resetting the RTS151 using a small tool to turn off the LED.

Wiring Diagrams for Various Detectors

Wiring Diagram for RTS151 to DNR 2-Wire Duct Smoke Detector

Details two methods for wiring the RTS151 to a DNR 2-wire duct smoke detector.

Wiring Diagram for RTS151 to DH100 ACDC 4-Wire Duct Smoke Detector

Illustrates the wiring connections between the RTS151 and the DH100ACDC detector.

Wiring Diagram for RTS151 to DH100 2-Wire Duct Smoke Detector

Provides the wiring scheme for connecting the RTS151 to a DH100 2-wire duct smoke detector.

Wiring Diagram for RTS151 to DH400 ACDC Duct Smoke Detector

Shows the specific wiring configuration for the RTS151 with a DH400ACDC detector.

Wiring Diagram for RTS151 to Beam1224;Beam1224 S Smoke Detector

Details the wiring for integrating the RTS151 with Beam1224 and Beam1224S detectors.

Three-Year Limited Warranty

Summary

Specifications

General Information

RTS151 Contents

Wiring of RTS151

Wiring Diagram for RTS151 to D4120 4-Wire Duct Smoke Detector

Illustrates the connection of the RTS151 to a D4120 4-wire duct smoke detector.

Wiring Diagram for RTS151 to D2-2 Wire Duct Smoke Detector

Shows how to wire the RTS151 to a D2-2 wire duct smoke detector, including test coil connections.

Operation

Test Function

Procedure for activating the test function using a magnet on the RTS151.

Alarm Indication

Describes the delay before the alarm LED lights up when the test function is active.

Reset Function

Instructions for resetting the RTS151 using a small tool to turn off the LED.

Wiring Diagrams for Various Detectors

Wiring Diagram for RTS151 to DNR 2-Wire Duct Smoke Detector

Details two methods for wiring the RTS151 to a DNR 2-wire duct smoke detector.

Wiring Diagram for RTS151 to DH100 ACDC 4-Wire Duct Smoke Detector

Illustrates the wiring connections between the RTS151 and the DH100ACDC detector.

Wiring Diagram for RTS151 to DH100 2-Wire Duct Smoke Detector

Provides the wiring scheme for connecting the RTS151 to a DH100 2-wire duct smoke detector.

Wiring Diagram for RTS151 to DH400 ACDC Duct Smoke Detector

Shows the specific wiring configuration for the RTS151 with a DH400ACDC detector.

Wiring Diagram for RTS151 to Beam1224;Beam1224 S Smoke Detector

Details the wiring for integrating the RTS151 with Beam1224 and Beam1224S detectors.

Three-Year Limited Warranty

Overview

The System Sensor RTS151 is an automatic fire detector accessory designed to facilitate the remote testing of fire detectors. This device is intended to be used in conjunction with various System Sensor smoke and beam detectors, allowing for convenient testing and resetting from a remote location. Its primary function is to provide a means to initiate a test sequence and observe alarm indications without direct access to the detector itself, which can be particularly useful for detectors installed in hard-to-reach areas.

Function Description:

The RTS151 serves as a remote interface for fire detection systems. When activated, it sends a signal to the connected smoke or beam detector, initiating a self-test sequence. During this test, the detector simulates an alarm condition. If the detector is functioning correctly, it will enter an alarm state, which is then indicated on the RTS151 by the illumination of its alarm LED. This provides a visual confirmation that the detector is operational and capable of detecting a fire condition.

Beyond testing, the RTS151 also offers a remote reset capability for certain System Sensor detector models. After a test or an actual alarm event, the detector can be reset from the RTS151, returning it to its normal monitoring state. This eliminates the need to physically access the detector to clear an alarm or test condition, streamlining maintenance procedures.

The device is designed for flexibility in installation, capable of being mounted in a single gang box or directly on a wall or ceiling. Its compact dimensions and light weight make it suitable for various installation environments.

Usage Features:

To initiate a test, a user simply places and holds the painted side of the provided M02-04 test magnet to the designated test location on the RTS151. Upon activation, there will be a brief delay, typically up to 40 seconds, depending on the specific detector type being tested, before the alarm indicating LED on the RTS151 illuminates. This delay accounts for the time required for the detector to complete its self-test and signal an alarm. The illumination of the red LED confirms that the connected detector has successfully entered an alarm state, indicating its proper functioning.

For resetting the detector, a small tool, with a maximum diameter of 1/8 inch, is gently inserted into the reset hole on the RTS151 until it stops. This action will turn off the alarm LED and reset the connected detector, returning it to its normal monitoring mode. It's important to note that the RTS151's reset function is compatible only with specific System Sensor detector models, and users should consult the detector's installation instructions for compatibility details.

The RTS151 is compatible with a range of System Sensor detectors, including 4-wire and 2-wire duct smoke detectors (such as D4120, DH100ACDC, DH100, DH400ACDC, and DNR models) and beam smoke detectors (BEAM1224/BEAM1224S). The specific wiring configurations vary depending on the detector model, and detailed wiring diagrams are provided in the manual to guide installers. For certain models, like the D2-2wire duct smoke detector, the RTS151's test coil circuit requires an external UL-listed 24 VDC power supply. Additionally, for these models, an accessory coil (part number DCoil or Coil, depending on the detector series) must be installed separately to enable the remote test station functionality.

In Canadian applications, the RTS151 is intended to be located in the same room as the smoke detector and within 60 feet of the unit, adhering to specific regional installation guidelines.

Maintenance Features:

The RTS151 itself requires minimal maintenance beyond ensuring its proper installation and connection to the detector. The primary maintenance aspect involves its use in testing the connected fire detectors. Regular testing of fire detection systems is crucial for ensuring their reliability and compliance with safety standards. The RTS151 simplifies this process by allowing personnel to perform functional tests from a convenient location, reducing the need for ladders or specialized equipment to access detectors in high or difficult-to-reach areas.

The device's design, with a clear alarm LED and a simple reset mechanism, provides straightforward visual feedback and operational control. Should any issues arise with the RTS151 or the connected detector, the detailed wiring diagrams in the manual serve as a valuable resource for troubleshooting. The manual also emphasizes the importance of consulting the National Fire Protection Association (NFPA) codes, standards, and recommended practices, as well as local codes and the requirements of the local authority having jurisdiction, for the proper installation and use of the product. This ensures that the entire fire detection system, including the RTS151, operates effectively and safely.

The RTS151 is a replacement for the RTS451, indicating an evolution in design and functionality to meet ongoing needs in fire detection system maintenance. Its robust construction and clear operational indicators contribute to its ease of use and long-term reliability within a fire safety system.

System Sensor RTS151 Specifications

General IconGeneral
CategoryTest Equipment
TypeRemote Test Station
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity10% to 93% non-condensing
MaterialPlastic
DeviceRTS151
CompatibilityCompatible with System Sensor devices
MountingSurface Mount
Weight0.5 lbs
Wiring18 AWG to 12 AWG

Related product manuals