Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
P1–Cooling
Auto
Setthepumpcontrolforthe
coolingcoiltoAuto,OnorOff
Firedamper
Auto
SettheFiredampertoAuto,
OpenorClose
Note:
Needstobeactivatedinorder
tobevisiblehere
Congurationofredamper
functionsaremadeatSystem
level
Outdoorair
damper
Auto
SettheOutdoorairdamperto
Auto,OpenorClose
→Settings
Inthismenugroupthesettings
fortheactivatedfunctionsare
available.Dependingonwhich
choiceshavebeenmadeinthe
congurationmenusomeofthe
possiblealternativesmaynot
bedisplayed.
→Controltemp
Supplyair
control
P-band:
33.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
Roomcontrol
P-band:
100.0°C
I-time:300.0
sec
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinfo
Shutdownmode
P-band:
100.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
TA450-4500
OperationandMaintenanceInstructions
132616
16
SystemairSverigeAB