7 For Topvex with control system sw 3.X
1 Reset the CEM15 by pressing the reset button while the
CEM15 is powered.
2 Connect a E3-DSP control panel
3 On first start up the controller will start a program for
downloading an application to the main memory.
4 The start screen is displayed.
→Application
System
Communication
Time/Date
Input/Output
Use the up and down arrows to move the cursor to Application and press the
right arrow to view available applications.
→Expansion unit 1
Expansion unit 2
Expansion unit 5
Expansion unit 6
Move the cursor to Expansion unit 1 and press the right arrow to select.
Title:
Expansion unit 1
Activate? No
Press OK and change Activate to Yes. Press OK.
The most recently loaded application will be entered into memory. This will
take approximately 30 seconds. The application start screen is displayed.
7.1 To set up pre-heating function
Function with expansion unit. Log on with admin rights, 3333.
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
* Access rights * Log on Log on
Enter password xxxx Actual
level: None
Log on to service level by entering a 4-digit code. After
reaching the desired level go back with “LEFT” arrow
(press 2 times) on the control panel.
Standard code from factory to enter service level is
2222. Back to operator level: 1111. To enter Admin lev-
el code: 3333.
→Configuration →Communication Function port2 Exp and ext
display
→Corrigo E15
→Input/Output →AI AI3:
Extra unit temp Raw value: NaN
Compensation: 0.0 °C
→AI exp1 AI1 Exp1:
Sign: Outd temp Raw value: 0.0
Compensation: 0.0 °C