16
|
Operation
Example 6: Alarm configuration
Configuration > Alarms
2020–10–22
Alarm delay at start up
60 s
Search alarm no: 53
Filter alarm supply air >
Air and temperature control >
Extra functions
>
Extra sensors and alarms
>
Fire/Smoke >
Component malfunction >
Manual operation and warnings >
Configuration > ... > Filter alarm supply air
2020–10–22
Action: No action
Level: Class B
Delay:
300 s
Limit X1: 0 m
3
/h
Limit Y1: 10 Pa
No: 53
Limit X2: 2000 m
3
/h
Limit Y2: 150 Pa
Name:
Filter alarm supply air
Original name: Filter alarm supply air
6.1.6 System information
Shows information about the air handling unit, installation site, control unit, communication and the
Systemair product. To enter information, such as site specific unit name or server partner’s contact
information, go to System information setup with user level Service.
Example 7: System information
System information
2020–10–22
Unit information
Installation address
Service partner
Communication
Access Control Unit
Systemair product
System information setup >
214959 | A004

Other manuals for SystemAir Topvex SC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SC and is the answer not in the manual?

SystemAir Topvex SC Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SC
CategoryAir Handlers
LanguageEnglish

Related product manuals