4.4Freecoolingdescription
Thisfunctionisusedduringthewarmperiodtosaveenergybyusingcoldoutdoorair,e.g.duringnight
time,tocooldownthebuilding.
Note:
ThefollowingisonlyvalidifthefreecoolingfunctionissettoActiveintheprogrammenu.
Freecoolingisonlyactivatedwhenthefollowingstartingconditionsaremet.
Startingconditions:
Lessthan4dayshavepassedsincetheunitwaslastinrunningmode
Theoutdoortemperatureduringthepreviousrunningperiodexceededasetlimit(+22°C)
Itisbetween00:00and07:00:00intheday(settable)
Thetimeroutputsfornormalspeed,ExtendedrunningnormalandExternalstopareOff
AtimechannelwillbeOnsometimeduringtherecentlystarted24hours.
Theunitchecksthenighttemperature(indoorandoutdoortemperature)during3minutesattheset
startinghourwhenthefansarestartedsothatthesensorscanperformatemperaturemeasurement.If
aboveconditionsaremetthefreecoolingfunctionisstarted,ifnottheunitgoesbacktoOFFposition.
Iftheoutdoorsensorisnotlocatedintheoutdoorairinletductandaroomsensorhasbeenselected,
theunitwillnotstartfreecoolingaslongasallthetemperaturesarenotwithinthestartandstop
temperatureintervals.
Stopconditions:
Outdoortempabovethesetmaxvalue(+18°C)orbelowthesetminvalue(condensationrisk,+10°C)
Theroomtemp/extractairtempisbelowthesetstopvalue(+18°C)
Oneofthetimeroutputsfornormalspeed,ExternalstoporExtendedrunningnormalisOn
Thetimehaspast07:00:00.
Whenfreecoolingisactive,thefansrunatnormalspeedorthesetvalueforpressure/owcontroland
thedigitaloutputFreecoolingisactive.TheoutputsY1-Heating,Y2-Heatexchangerand
Y3-Coolingareshutdown.Afterfreecoolinghasbeenactivated,theheatingoutputisblockedfor60
minutes(congurabletime).
5Maintenance
5.1Important
Danger
MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
Warning
AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating
partsthathavenotcometoacompletestandstill.
Bewareofsharpedgesduringmountingandmaintenance.Useprotectiveclothing.
TopvexSR/TR03,SR/TR04,SR/TR06OperationandMaintenanceInstructions