Page #55 background image
Page 54
Technical data
VLC ELN 904 1004 1104 1204
Power supply V/ph/Hz 400 (±10%) / 3 / 50
Number of circuits 2 2 2 2
Capacity steps % 28-50-78-100 25-50-75-100 23-50-73-100 25-50-75-100
Refrigerant
Type / GWP R410A / 2.088
Charge 1/2
(1)
kg 27/27 30,5/30,5 34/34 37,5/37,5
tCO
2
eq 56,4/56,4 63,7/63,7 71,0/71,0 78,3/78,3
Compressor
Type Scroll
Number 4 4 4 4
Start-up type Direct
N°of loading stages 0/100 0/100 0/100 0/100
Condenser
Type Coil
Refrigerant connections
Inlet diameter inch 1 1/8” 1 1/8” 1 1/8” 1 1/8”
Outlet diameter inch 2 1/8” 2 1/8” 2 1/8” 2 1/8”
Weights
Shipping weight kg 1613 1662 1679 1682
Additional Weights
HSE* versions kg 40 40 40 40
Dimensions
Length mm 4300 4300 4300 4300
Width mm 1100 1100 1100 1100
Height mm 2300 2300 2300 2300
(1) The value is representing the contribution to the global refrigerant charge given by the standard unit only. Contribution of connection piping and remote evaporator
is not included here.
(*) High Efficiency Units (HSE) with inverter fans.