Installation and maintenance manual
Manuel d'installation et de maintenance
Installations- und Wartungshandbuch
Manuale di installazione e di manutenzione
Manual de instalación y de mantenimiento
SYSCROLL 20-35 Air CO/HP
Part number / Code / Code / Codice / Código : 361790
Supersedes / Annule et remplace / Annulliert und ersetzt / Annulla e sostituisce /
Anula y sustituye : None / Aucun / Nicht / Nulla / Ninguno
Notified Body / Organisme Notifié / Benannte Zertifizierungsstelle / Organismo
Notificato / Organismo Notificado N°. 1115
20
!
33 kW
21
!
35 kW
ISO 9001 certified management system

Questions and Answers

  • K
    Krystal GutierrezAug 18, 2025
    How to troubleshoot excessive noise in my SystemAir SYSCROLL 20-35 Air Heat Pump?
    • K
      Karen RamosAug 18, 2025
      If your SystemAir Heat Pump is making excessive noise, start by checking the clamping brackets of the lines for vibration. If the noise is a whistler emitted by the thermostatic expansion valve, consider refilling. Inspect the dehydrating filter. If the compressor is noisy, it may have seized bearings, requiring a compressor replacement. Also, ensure that the compressor’s locknuts are tightened.
  • F
    Frank MorenoAug 21, 2025
    What to do if my SystemAir SYSCROLL 20-35 Air activates the HP alarm and stops?
    • C
      Clinton HallAug 21, 2025
      If your SystemAir Heat Pump activates the HP alarm and stops, it could be due to several reasons. Check the operation of the pressure switch, and replace it if it’s defective. Ensure that the delivery valve is fully open; if it’s faulty, replace it. If there are substances with condensable gases in the circuit, drain the circuit. Also, check the condenser fan's cables and motor; if they are defective, repair or replace them.
  • A
    astevensAug 25, 2025
    Why is my SystemAir SYSCROLL 20-35 Air running but not cooling?
    • J
      Joyce Gallegos MDAug 25, 2025
      If your SystemAir Heat Pump continues to work but isn't cooling, it could be due to an insufficient charge of refrigerant, in which case you should refill it. Alternatively, the dehydrating filter might be clogged, requiring replacement.
  • P
    Patrick BrownAug 27, 2025
    Why is the liquid line too hot on my SystemAir Heat Pump?
    • C
      courtneybennettAug 27, 2025
      If the liquid line of your SystemAir Heat Pump feels too hot, it likely indicates an insufficient charge of refrigerant. Identify and remove the cause of the loss of charge, then refill the system.
  • C
    castillorobertAug 31, 2025
    What causes the LP alarm and unit stop in my SystemAir Heat Pump?
    • N
      Nicholas DennisAug 31, 2025
      If your SystemAir Heat Pump activates the LP alarm and stops, it may be due to a gas leak; identify and remove the leak. It could also be caused by an insufficient charge, requiring a refill.
  • L
    Lisa PughSep 3, 2025
    Why is there ice on the suction line of my SystemAir SYSCROLL 20-35 Air Heat Pump?
    • S
      sarahaguilarSep 3, 2025
      If you notice ice forming on the suction line of your SystemAir Heat Pump, it could be due to a wrong calibration of overheating; increase overheating to resolve this. Also you should check the charge.
  • S
    Suzanne WilsonSep 6, 2025
    What causes frosting on the liquid line of my SystemAir SYSCROLL 20-35 Air?
    • K
      Kristen CannonSep 7, 2025
      If you notice frosting on the liquid line of your SystemAir Heat Pump, it may be because the valve of the liquid line is partially closed; ensure that all valves are fully open. Alternatively, the liquid filter could be clogged, requiring replacement of the cartridge or the filter itself.
  • J
    jeff56Sep 10, 2025
    What causes low oil level in the compressor of my SystemAir SYSCROLL 20-35 Air Heat Pump?
    • L
      Lauren JenningsSep 10, 2025
      If you observe a low oil level in the compressor of your SystemAir Heat Pump, it could be due to one or more gas or oil leaks in the circuit; identify and remove these leaks. It may also indicate a mechanical failure of the compressor, requiring intervention from a Service Centre. Another potential cause is an anomaly of the oil heater of the compressor’s base; check the electric circuit and the resistor of the heater of the motor base, and replace any defective components.
  • T
    Tracey JohnsonNov 13, 2025
    What to do if one or both compressors are not working in my SystemAir SYSCROLL 20-35 Air Heat Pump?
    • M
      mackenzie62Nov 13, 2025
      If one or both compressors in your SystemAir Heat Pump aren't working, several issues could be the cause. First, check the electric circuit for any ground dispersions and short circuits, and inspect the fuses. If the HP pressure switch has intervened, reset it along with the control panel, then restart the appliance, making sure to identify and remove the cause that enabled the pressure switch. Also, check for loosened terminals and tighten them. If there's a halt due to thermal overload, check the operation of check and safety devices and remove the cause. Confirm that the wiring of check and safety devices is correct. Ensure the line voltage is adequate; if it's too low, address the system issues or inform the Energy Distributor if the problem is with the distribution network. Furthermor...

Summary

FOREWORD

1.2 Warranty

Details warranty conditions, voiding clauses, and required maintenance.

SAFETY

2.1 Foreword

Lists installation compliance requirements with EU directives.

2.4 General precautions

Lists general safety precautions for operation and handling.

2.5 Residual risk precautions

Details precautions for control system, mechanical, and electrical risks.

2.6 Maintenance safety precautions

Outlines safety measures for maintenance personnel and procedures.

2.8 Refrigerant Safety Data

Details safety data and regulations for R410A refrigerant.

2.9 Lubricant Oil Safety Data

Details safety data and regulations for Polyester Oil (POE).

INSTALLATION

4.1 Installation Site

Details site selection criteria for optimal performance and safety.

4.6 Power supply

Covers power supply requirements, grounding, and electrical connections.

START-UP

5.1 Preliminary checks

Lists essential checks before unit start-up and personnel arrival.

5.2 Start-up sequence

Provides the sequence for starting the unit for the first time.

CONTROL

6.4 Alarm list

Lists all possible alarms, their codes, and operational status.

TECHNICAL DATA

8.3 Electrical data

Lists electrical data for the unit, compressor, fans, and pumps.

MAINTENANCE

9.1 General requirements

Outlines general requirements for unit maintenance and service.

9.2 Planned maintenance

Provides a schedule for planned maintenance inspections.

9.3 Refrigerant charge

Details procedures and precautions for charging refrigerant.

TROUBLESHOOTING