TAC Xenta 511 and 911 Handbook 2 TAC Xenta 511
10 (32), 0-004-7870-0 (EN) TAC AB, 16 May 2003
2.3.1 Information from the Network Administrator
Determine whether fixed IP address or DHCP (Dynamic Host Config-
uration Protocol: IP address is assigned by the system) will be used.
Complete this “Setting List for Configuration”.
• IP address (If fixed; e.g. 172.20.4.21):.............................................
• Subnet mask (If fixed; e.g. 255.255.0.0): .........................................
• Default Gateway (e.g. 172.20.2.100):...............................................
• DNS (e.g. 192.165.248.22):..............................................................
• Web site name:..................................................................................
• Domain name: ..................................................................................
• Host name:........................................................................................
For explanations, please consult the Engineering TAC Xenta 511 man-
ual.
2.3.2 Power and Hyperterminal Connections
1 G and G0: Supply 24 V power to terminals.
Minimum cross-sectional area 0.75 mm² (AWG-19).
All equipment that is connected to the unit must comply with the
following standards:
• EN 60 742 (or other relevant safety standard) for the device(s)
that provide an ELV-type power supply (normally 24 VAC) to
the unit and other connected equipment.
• EN 61 010 or IEC 950 (or other relevant safety standard) for
computers and other equipment supplied by power line voltage.
• C1 and C2 (LonWorks connection, not used by Web Browser):
standard unshielded (UTP) or shielded (STP) twisted pair cable.
2 Connect a serial cable between the PC and the Xenta 511 RS232 B.
G G0 C1 C2
1 2 3 4
~ 0
24 V AC
(19-40 V DC)
}
LonWorks
comm.
TAC Xenta 511 mounting and electrical connections