TAC Xenta 511 and 911 Handbook 2 TAC Xenta 511
TAC AB, 16 May 2003 0-004-7870-0 (EN), 17 (32)
2.6 Technical Data for the TAC Xenta 511
Supply voltage...............................................24 V AC ±20%, 50/60 Hz
...................................................................................or 19–40 V DC
Power consumption.................................................................max. 5 W
Transformer sizing .........................................................................5 VA
Ambient temperature:
Storage......................................–20 °C to +50 °C (-4 °F to +122 °F)
Operation................................ ±0 °C to +50 °C (+32 °F to +122 °F)
Humidity................................................ max. 90% RH non-condensing
Mechanical:
Enclosure..............................................................................ABS/PC
Enclosure rating ........................................................................IP 20
Dimensions......... see section 2.2 “Hardware Installation” on page 9
Weight......................................................................0.2 kg (0.44 lb.)
Real time clock:
Accuracy at +25 °C..........................................±14 minutes per year
Power outage protection..............................................................72 h
Communication:
Modem .................................. 9,600-57,600 bps RS232A, RJ45, 8-p
PC, configuration ............................................... RS232B, RJ10, 4-p
LONWORKS............................................TP/FT-10, terminal block
Ethernet......................................................TCP/IP, 10Base-T, RJ45
Storage:
Nonvolatile
System software, applications, files......................................... 8 MB
External memory, MMC
Files...................................................................................4-128 MB
Agency Compliances:
Emission......................................C-Tick, EN 50081-1, FCC Part 15
Immunity ........................................................................EN 50082-1
Safety:
CE...................................................................................EN 61010-1
UL 916 ...........................................Energy Management Equipment
ETL listing .................................................. UL 3111-1, first edition
....................................................... CAN/CSA C22.2 No. 1010.1-92
Flammability rating...........................................................UL 94V-0
Part numbers:
Electronics part TAC Xenta 511.....................................0-073-0811
Terminal part TAC Xenta 400 ........................................0-073-0902
TAC Xenta: PC to Serial Kit...........................................0-073-0917
TAC Xenta: Serial Link Kit............................................0-073-0918
TAC Xenta: General Serial Kit.......................................0-073-0919
TAC Xenta: Programming Serial Kit..............................0-073-0920