13
PRSU Series, Operating Instructions Manual (Revision 1.0)
+24V
DC
: 2.5W, 24V
AC
: 2.5VA
Maximum Short Circuit Resistance
Maximum Signal Wires Resistance
2 x 1.5 mm
2
solid wire
2 x 1.5 mm
2
stranded wire-end ferrule
UL: Use 60/75°C copper wire only!
Max. Conductor Length (input circuit)
2 x 100m (Single channel)
4 x 100m (Dual channel)
AgSnO
2
or comparable material
Max. Switch/Relay Current
6A (individual), 13.8A (combined)
Max. Switching Capability (per relay)
DIN EN 60947-5-1
Creeping Distance and
Clearance
-EN 50178 at pollution grade 2, over voltage category 3 / 250V
-Basis isolation: over voltage
category 3 / 250 V
NO contact: 6.3A brief or 4A inert
Short Circuit Withstand
(IEC60947-5-1)
Weld Free Protection at I
PSCC
≥1kA SCPD
(Short Circuit Protection Device)
(Fuse links), size D01
acc IEC IEC60269-1; IEC60269-3-1; VDE036-
T301
Restarting Readiness Time (minimum switch off
time the inputs)
24V DC: < 30 ms, 24V AC: < 70ms
Click-fastening for DIN-Rail
Torque Setting for Connection Terminals
0.5 Nm (min), 0.6 Nm (max)
UL: Overtorquing may cause
enclosure breakage
-25°C ... +55°C ( UL:…+40°C)
Shock Resistance of N.O Contacts
Performance Level e, Cat. 4