9
PRSU Series, Operating Instructions Manual (Revision 1.0)
2. Manual:
In this operating mode, the output relay coils will de-energize upon
the closure of conductors within the monitored sensor/switch system.
The coils will not energize again until the closure is broken and a
RESET signal is manually generated by the operator (via a mechanical
N.O. pushbutton or switch).
3. Conditional:
In this operating mode, the RESET signal cannot propagate
unless all of the following conditions are met:
- The contacts have opened in the monitored sensor/switch.
- The machine primary control elements (MPCE 1 and MPCE 2)
have closed.
- A manual RESET signal is subsequently generated by an
operator pressing the “Start” pushbutton.
Figure 6: RESET Mode (Manual) Configuration
Figure 7: RESET Mode (Conditional) Configuration