EasyManua.ls Logo

TECE RD 20203 - Page 22

TECE RD 20203
151 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
DAN
NOR
FIN
SWE
ENG
POL
RUS
ENG
Device overview
No. Description Setting
032
Restricted operation
Switch-over of the room control unit operat-
ing lock between “Standard” and “Restricted
operation”.
0 = deactivated
1 = activated
Standard: 0
040
External sensor (only Control)
Registration of an external room/floor sensor
or dew point sensor (TPS). The registration
of a room sensor (1) deactivates the internal
sensor. If a floor sensor (2) is used, the min-
imum floor temperature can be set via the
Settings menu in the function “External floor
sensor”.
0 = no external
sensor
1 = room sensor
2 = floor sensor
3 = dew point
sensor (TPS)
Standard: 0
A floor sensor (2) can only be used in
the “Heating”( ) voperating mode.
041
Correction of actual temperature of
external sensor (only Control)
Corrects a deviating measurement of the ac-
tual temperature.
-2 ... +2°C
Standard: 0 °C
042
Inverting the dew point sensor
(Control only)
Reverses the control direction of the dew
point sensor registered with the device.
NO = Normally Open
NC = Normally Closed
0 = NC
1 = NO
Standard: 0
050
Duration of the display illumination
Sets the duration of further illumination of
the display after use.
0 ... 30sec.
in 5 second incre-
ments
Standard: 15sec.
090
Signalling of switching output
Signalises the control of switching outputs by
a flashing heating resp. cooling symbol.
0 = deactivated
1 = activated
Standard: 1

Table of Contents