1
1 - 24
1-1. Unit Specifications
Concealed-Duct Type DSAFP255R x 2 / GRFP255L
Capacity [minimum~maximum] kW
BTU/h
Air circulation (Hi/Me/Lo) m3/h
Moisture removal (High) Liters/h
External static pressure (High) Pa(mmAq)
Voltage rating V
Available voltage range V
Running amperes* A
Max–Running amperes** A
Power input kW
C.O.P W/W
Max. Starting amperes A
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation sound Indoor - Hi/Me/Lo dB - A
Outdoor - Hi dB - A
Color (Approximate value) Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing length m (ft.)
Limit of tubing length at shipment m (ft.)
Limit of elevation difference m (ft.)
between the two units
Refrigerant tube Narrow tube mm (in.)
outer diameter Wide tube mm (in.)
Refrigerant amount at shipment kg
DIMENSIONS & WEIGHT
Unit dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Package dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Net weight kg (lb.)
Shipping weight kg (lb.)
Shipping volume
m
3
(cu. Ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
783 (30-26/32)
32 (71)
Indoor unit
630 (24-26/32)
358 (14-3/32)
Microprocessor/I.C.thermostat
Outdoor unit
Outdoor unit is lower than indoor unit : 15 (49)
37 (82)
R410A - 3.6
5~30 (16~98)
0.334 (11.8)
Outdoor unit is higher than indoor unit : 30 (98)
Munsell 1Y 8.5/0.5
52
–
Rotary(SANYO)
9.52 (3/8)
–
15.88 (5/8)
Field supply
–
1,191 (46-28/32)
ELECTRICAL RATINGS
220 230
FEATURES
2.85 2.83
0.552 (19.5)
100 (220)
50 (5.1) : at shipment,92 (9.4) : using the booster cable
Max.head 50 cm above drain connection (25A , OD32mm)
310 (12-7/32)
1,000 (39-12/32)
Cooling
240
21.3 20.6
Wireless : REM HL
4.39 4.42 4.45
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
22.2
2.81
PERFORMANCE
Outdoor Unit GRFP255L
POWER SOURCE 220 - 230 - 240 V/1 phase/50/60 Hz
MODEL No. Indoor Unit DSAFP255R x 2
109 (240)
34/30/27, (38/34/30 : using the booster cable)
50 (164)
12.5 [2.7~14.0]
42,500 [9,200~48,000]
7.0 (3.5x2)
198 - 264
2,160/1,800/1,560 (1,080/900/780x2)
ON/OFF 72-hours
3 and Automatic control/Variable
Wired : REM HW
04-163 Sanyo-1_p30-61 7/28/04 5:46 PM Page 56