1 - 28
Capacity [minimum~maximum] kW
BTU/h
Air circulation (Hi/Me/Lo) m3/h
Moisture removal (High) Liters/h
External static pressure (High) Pa(mmAq)
Voltage rating V
Available voltage range V
Running amperes* A
MaxRunning amperes** A
Power input kW
C.O.P W/W
Max. Starting amperes A
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation sound Indoor - Hi/Me/Lo dB - A
Outdoor - Hi dB - A
Color (Approximate value) Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing length m (ft.)
Limit of tubing length at shipment m (ft.)
Limit of elevation difference m (ft.)
between the two units
Refrigerant tube Narrow tube mm (in.)
outer diameter Wide tube mm (in.)
Refrigerant amount at shipment kg
DIMENSIONS & WEIGHT
Unit dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Package dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Net weight kg (lb.)
Shipping weight kg (lb.)
Shipping volume
m
3
(cu. Ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor unit Outdoor unit
310 (12-7/32)
1,480 (58-9/32)
630 (24-26/32)
358 (14-3/32)
1,671 (65-25/32)
783 (30-26/32)
47 (104)
52
Munsell 1Y 8.5/0.5
50 (164)
Max.head 50 cm above drain connection (25A , OD32mm)
Rotary(SANYO)
40/37/33, (44/40/37 : using the booster cable)
15.88 (5/8)
R410A - 3.6
52 (115)
Field supply
5~30 (16~98)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
9.52 (3/8)
4.34 4.36 4.37
2.88 2.87 2.86
20.3
Outdoor Unit GRFP485L
POWER SOURCE 220 - 230 - 240 V/1 phase/50/60 Hz
Cooling
12.5 [2.7~14.0]
42,500 [9,200~48,000]
1,980/1,560/1,320
6.6
ELECTRICAL RATINGS
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
78 (8.0) : at shipment, 113 (11.5) : using the booster cable
220 230
340 (13-3 /8)
1330 (52-3 /8)
MODEL No. Indoor Unit DSAFP485R
Wired : REM HW Wireless : REM HL
PERFORMANCE
240
198 - 264
22.0 21.1
FEATURES
Microprocessor/I.C.thermostat
1230 (48- 7/16)
940 (37)
0.468 (16.5) 0.552 (19.5)
ON/OFF 72-hours
3 and Automatic control/Variable
1-1. Unit Specifications
Concealed-Duct Type DSAFP485R / GRFP485L
04-163 Sanyo-1_p30-61 7/28/04 5:46 PM Page 60