1-11. Installation Instructions
TUBING LENGTH
(A) Single type
Keep refrigerant tubing between the indoor and
outdoor units as short as possible.
The length of the refrigerant tubes between the
indoor and outdoor units is limited by the elevation
difference between the 2 units. During tubing work,
try to make both the tubing length (L) and the dif-
ference in elevation (H1) as short as possible.
Refer to Table 1-5.
Table 1-1
Single
L
H1
Indoor unit type 71 types 100, 125 types
Maximum allowable tubing length 50 m 50 m
Charge-less tubing length (actual length) 30 m 30 m
Additional refrigerant charge per 1 m 40g
Minimum tubing length 3 m 5 m
04-309 Sanyo-1_p96-127 10/27/04 2:10 PM Page 118