1. Specifications
1
12
3
4
5
I-118
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit :DSAV480R5TAA Outdoor Unit :GRV480R7TAA
GRV480L7TAA
Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 1.48 / 1.58 1.24 / 1.31 7.7 / 7.72 8.5 / 8.53
kW 310 / 360 0.26 / 0.29 4.14 / 4.16 4.71 / 4.81
Full load conditions
A 1.48 / 1.58 1.24 / 1.31 8.8 / 8.82 9.62 / 9.66
kW 310 / 360 0.26 / 0.29 5 / 5.04 5.57 / 5.69
Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58
Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 1.48 / 1.58 1.24 / 1.31 8.89 / 8.91 9.71 / 9.75
kW 310 / 360 0.26 / 0.29 5.06 / 5.08 5.63 / 5.73
Full load conditions
A 1.48 / 1.58 1.24 / 1.31 9.4 / 9.41 10.23 / 10.25
kW 310 / 360 0.26 / 0.29 5.38 / 5.42 5.95 / 6.07
Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions:Indoor Air Temperature35°C DB / 25°C WB
Outdoor Air Temperature43°C DB
Heating:
Rating Conditions:Indoor Air Temperature20°C DB
Outdoor Air Temperature7°C DB / 6°C WB
Full Load Conditions:Indoor Air Temperature27°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB