EasyManua.ls Logo

Technibel DSAV480R5TAA - Other Component Specifications

Default Icon
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Specifications
1
12
3
4
5
I-52
1-3 Other Component Specifications
4-Way Air Discharge Semi-concealed Type
MODEL NO.Indoor UnitCAV250 ~480R5TAA
Power Transformer ATR-II215TA
Rated
Primary VAC, Hz 230 V, 50 Hz
Secondary 10.2 V 1.4 A
14 V 0.5 A
Coil resistance WHT – WHT : 84 , BRN – BRN : 0.7
RED – RED : 2.7
Thermal cut off temperature ˚ C 145
Thermistor (Coil sensor) : TH2, 3, 4 PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S26 , PBC-41E-S36
Resistance K -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %
-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %
0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %
5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %
10 ˚C : 9.7 ± 5 %
Thermistor (Room sensor) : TH1 KTEC-35-S6
Resistance K 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %
5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %
10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %
20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %
30 ˚C : 4.0 ± 5 %
Electronic expansion valve
Valve bodyIKV-24D12(CAV250R5TAA)
HKV-30D16(CAV360-480R5TAA)
CoilDKV-MOZS582E0(CAV250R5TAA)
EKV-MOZS584E0(CAV360-480R5TAA)
Drain pump WP20SL-21
Rated 230 V, 14.7 W
Float switchFS-0218-102(CAV250R5TAA)
FS-0218-103(CAV360-480R5TAA)
Rated (Contact rated) DC 12 V, 25 W

Table of Contents

Related product manuals