EasyManua.ls Logo

Technibel DSAV480R5TAA - (B) Outdoor Units

Default Icon
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Specifications
1
12
3
4
5
I-46
1-2 Major Component Specifications
(B) Outdoor Unit
MODEL No.GRV250R5TAA
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Controller P.C.B. Ass'y CR - CR253GHL5 (Microprocessor)
Control circuit fuse 250 V, 3.15 A
Compressor Rotary (Hermetic)
Model ..... number C - RN220H5B
Source 220 - 240 V / 1 phase / 50 Hz
Nominal output W 2200
Compressor oil cc 1500
Coil resistance C – R : 0.76 , R – S : 3.52
(Ambient temperature 25 °C) C – S : 2.76
Safety devices
Overload relay models Internal type
Operating temperature Open °C160± 5
Close °C87± 11
Crank case heater 240V, 25 W
Refrigerant amount at shipment kg R407C - 3.2
High pressure switch ACB
-
1TB07
Set pressure OFF kg/cm
2
32 (3.2 MPa)
ON kg/cm
2
24 ± 2.0 (2.4 ± 0.2 MPa)
Fan Propeller
Number...diameter mm 1 ..... ø460
Air circulation (Hi)m
3
/h2800
Fan speeds 3 (AUTO)
Fan motor
Model KFC6T - 91C5P
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252
Nominal output W 70
Coil resistance WHT BRN : 127.3 , VLT YEL : 15.0
(Ambient temperature 20°C) WHT VLT : 56.7 , YEL PNK : 7.2
Safety device Internal type
Operating temperature Open °C130± 8
Close °C79± 15
Run capacitor VAC, µF 440 V, 6 µF
Heat exchange
Coil Aluminium plate fin / Copper tube
Rows ..... fin pitch mm 2 ..... 1.8
Face area m
2
0.616
+ 0
– 1.5
+ 0
– 0.15

Table of Contents