1. Specifications
1
12
3
4
5
I-52
1-3 Other Component Specifications
4-Way Air Discharge Semi-concealed Type
MODEL NO.Indoor UnitCAV250 ~480R5TAA
Power Transformer ATR-II215TA
Rated
Primary VAC, Hz 230 V, 50 Hz
Secondary 10.2 V 1.4 A
14 V 0.5 A
Coil resistance Ω WHT – WHT : 84 , BRN – BRN : 0.7
RED – RED : 2.7
Thermal cut off temperature ˚ C 145
Thermistor (Coil sensor) : TH2, 3, 4 PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S26 , PBC-41E-S36
Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %
-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %
0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %
5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %
10 ˚C : 9.7 ± 5 %
Thermistor (Room sensor) : TH1 KTEC-35-S6
Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %
5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %
10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %
20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %
30 ˚C : 4.0 ± 5 %
Electronic expansion valve
Valve bodyIKV-24D12(CAV250R5TAA)
HKV-30D16(CAV360-480R5TAA)
CoilDKV-MOZS582E0(CAV250R5TAA)
EKV-MOZS584E0(CAV360-480R5TAA)
Drain pump WP20SL-21
Rated 230 V, 14.7 W
Float switchFS-0218-102(CAV250R5TAA)
FS-0218-103(CAV360-480R5TAA)
Rated (Contact rated) DC 12 V, 25 W