4
3 - TECHNICAL CHARACTERISTICS
(*) Gross value (without circulator) Single-phase / three-phase
NOMINAL OPERATING CONDITIONS
NOTE:
Water system pressure: 1,5 to 3 bar.
OPERA
TING LIMITS (pure water) (*)
(*) The limits indicated are those of the machine.
(**)
At 43
°
C outside air temperature, the max. temperature of the water outlet is limited to 18
°
C instead of 20
°
C.
PHRT 7 PHRT 9 PHRT 12 PHRT 16
+ 19° C + 19° C + 19° C + 19° C
+ 5° C + 5° C + 5° C + 5° C
- 5° C - 5° C - 5° C - 5° C
- 15° C - 15° C - 15° C - 15° C
+ 70° C + 70° C + 70° C + 70° C
+ 25° C + 25° C + 25° C + 25° C
+ 43° C (**) + 43° C (**) + 43° C (**) + 43° C (**)
+ 10° C + 10° C + 10° C + 10° C
+ 20° C (**) + 20° C (**) + 20° C (**) + 20° C (**)
+ 5° C + 5° C + 5° C + 5° C
Min. water outlet temperature
COOLING
Max. outside air temperature (dry)
Min. outside air temperature (dry)
HEATING
Max. outside air temperature (humid)
Min. outside air temperature (dry) for water
output temperature 50°C
Max. water outlet temperature
Min. outside air temperature (dry) for water
output temperature 55°C (max.)
Min. outside air temperature (dry) for water
output temperature 45°C (nominal)
Min. water outlet temperature
Max. water intlet temperature
Outside air temperature (dry) + 7° C
Outside air temperature (humid) + 6° C
Water outlet temperature + 45° C
Outside air temperature (dry) + 35° C
Water outlet temperature + 7° C
HEATING
COOLING
PHRT 7 PHRT 9 PHRT 12 PHRT 16
Heating capacity kW 6.90 9.00 / 9.00 10.70 / 12.70 15.20
kW 2.54 3.16 / 3.10 3.48 / 3.94 4.82
Water regime 40/45°C 2.72 2.85 / 2.90 3.06 / 3.22 3.15
Water regime 30/35°C 3.48 3.63 / 3.68 3.89 / 4.00 4.05
Total Max. kW 3.27 4.00 4.70 _
power consumption kW _ 4.00 5.10 7.00
Total Max. A 14.60 18.20 21.30 _
current consumption A _ 7.20 9.00 12.70
Nominal water flow
m
3
/h 1.24 1.58 1.87 / 2.16 2.70
4.40 4.40 5.20 / 6.00 7.50
Available pressure kPa 58.00 47.00 66.00 / 53.00 68.00
Cooling capacity kW 5.90 7.10 / 7.10 8.50 / 9.00 11.40
kW 2.54 3.14 / 3.09 3.31 / 3.73 4.98
(EER)* 2.32 2.26 / 2.30 2.57 / 2.41 2.29
Total Max. kW 3.27 4.00 4.70 _
power consumption kW _ 4.00 5.10 7.00
Total Max. A 14.60 18.20 21.30 _
current consumption A _ 7.20 9.00 12.70
Nominal water flow
m
3
/h 1.02 1.22 1.48 / 1.51 1.98
2.80 3.40 4.10 / 4.20 5.50
Available pressure kPa 64.00 59.00 82.00 / 80.00 84.00
10
-4
m
3
/s
1-phase
3-phase
1-phase
3-phase
Model
10
-4
m
3
/s
1-phase
3-phase
1-phase
3-phase
COOLING