2
MARKING
This product marked conforms to the essential requirements of the Directives:
- Low voltage no. 73/23 EEC, modified 93/68 EEC.
- Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 and 93/68 EEC.
- Pressure Equipment Directive No. 97/23/CE.
SUMMARY
1-Generalities ................................................................................... 2
2-Dimensions.................................................................................... 3
3-Installation ..................................................................................... 4
4-Connections................................................................................... 4
5-Options .......................................................................................... 7
6-Starting ........................................................................................ 12
7-Operation of µCHILLER electronic control .................................. 13
8-Maintenance ................................................................................ 19
9-Pressure curves........................................................................... 22
APPLIANCES FILLED WITH R 407 C
R 407 C
Fluid R 407 C, as opposed to R22, is not a pure fluid but a blend
composed of:
- 23% R 32 + 25% R 125 + 52% R 134 A.
The compressors approved for operation with this fluid are filled
beforehand with polyalcohol oil.
Contrary to mineral oil, it is very hygroscopic: it absorbs the
humidity of the ambient air very quickly. This can modify its
lubricant properties and lead in time to the destruction of the
compressor.
MAINTENANCE INSTRUCTIONS
1 - Never add oil to the appliance; the compressor is filled with
polyalcohol oil, a special oil which cannot tolerate the presence
of other oils.
2 - The instruments used for:
- filling,
- pressure measurements,
- emptying under vacuum,
- recovering the fluid,
must be compatible and only used for the R 407 C fluid.
3 - The weight of the refrigerant contained in the storage bottle must
be checked constantly. Do not use it from the moment the
remaining weight is less than 10% of the total weight.
4 - In the case of a new charge:
- do not use the charging cylinder,
- use a balance and a dip pipe type R 407 C cylinder,
- charge the weight of R 407 C as per the value indicated on the
unit’s identification plate,
- IMPORTANT: see instruction 3 above.
5 - The charge must be undertaken in liquid phase.
6 - In case of leakage, do not complete the charge: recover the
remaining refrigerant for recycling and perform a total charge.
Recovery, recycling or the destruction of the fluid must be done
in compliance with the laws in force in the country concerned.
7 - If the refrigerant circuit is opened, you must:
- avoid the entry of air into the circuit as much as possible,
- replace the filter drier,
- perform the "vacuum operation" at a minimum level of 0.3
mbar (static).
1 - GENERALITIES
The equipment must be installed, started-up and maintained by authorised and qualified personnel, in accordance with local
rules and professional standards.
The recommendations and instructions presented in the manual and on labels must be followed.
1.1 - GENERAL SUPPLY CONDITIONS
The units must be securely anchored to the truck’s trailer during transport.
Generally speaking, the material is transported at the consignee’s risk.
In the event of damages during transport, the consignee must notify the carrier by registered letter within three days following
delivery.
1.2 - VOLTAGE
Before carrying out any operation, check that the voltage indicated on the unit corresponds to the mains voltage.
Before servicing the unit, ensure that the electrical power supply has been shut off and warning signs installed.
1.3 - TECHNICAL AND PHYSICAL CHARACTERISTICS
See technical data.