EasyManua.ls Logo

Technoline EVO PLUS 1.000 PF - 2-7 Setup the UPS

Default Icon
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
LCD control panel introduction
1LEDfrom top to bottom: “alarm”, “bypass, “battery”, “inverter);
2On-Line UPS LCD display;3Buttons-FUNC button/OFF button/On button.
Indicator
Status
Description
Red
On
The UPS has an active alarm or fault.
Yellow
On
The UPS is in Bypass mode.
The UPS is operating normally on bypass
during High Efficiency operation.
Yellow
On
The UPS is on Battery mode.
Green
On
The UPS is operating normally on Oline.
2-7 Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using
extension cords.
For 208/220/230/240VAC models: The power cord is supplied in the UPS
package.
Step 2: UPS output connection
For socket-type outputs, simply connect devices to the outlets.
For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm
2
power cords for 3KVA (220/230/240VAC
models).
c) Upon completion of the wiring configuration, please check whether the